24
10.2.2 Setting to the medium
In case of doubt, carry out an application test to ensure the setting
(HIGH or LOW) which is best for the medium to be measured�
►
Select [MEdI], press [SET] for 5 s�
> [nonE] is displayed�
►
Set the requested value:
-[HIGH] for water and water-based media�
-[LOW] for oils and oil-based media�
MEdl
Then the unit changes to the operating mode� For further parameter setting the
menu can be opened�
10.2.3 Configuration of the display
►
Select [Uni] and set the unit of measurement: [cm], [inch]�
Factory setting: cm�
►
Select [SELd] and set type of indication:
-[L] = The level is indicated in cm or inch�
-[L%] = The level is indicated in percent of the final value of the
measuring range�
-[OFF ] = The display is switched off in the operating mode� When one
of the buttons is pressed, the current measured value is displayed for
30 s� The LEDs remain active even if the display is deactivated�
Uni
SELd
10.3 Offset setting
Set offset before setting the switching limits (SPx/FHx, rPx/FLx, OP)�
Otherwise, the switching limits shift by the value of the set offset�
►
Select [OFS] and enter the distance between bottom of the tank and
lower edge of the probe�
> Afterwards, display and switch points refer to the real level�
Factory setting: [OFS] = 0�