LR7009
Electronic level sensor
34
XX.X:
display value
A:
emptying
B:
overflow prevention
•
If SP1 is exceeded, output 1 switches (submersible pump ON). If the level is below rP1, output 1 is
reset (submersible pump OFF).
•
If SP2 is exceeded or if there is a wire break, output 2 is reset (OFF).
12.3 Storage tank
Monitoring of the acceptable range (alarm) and level control:
Switching output 1: refilling
SP1
upper preset value exceeded
Ò
finish refilling
rP1
below lower preset value
Ò
start refilling
OU1
hysteresis function, normally closed (Hnc)
Switching output 2: safety function min - max
FH2
max. value exceeded
Ò
alarm
FL2
below min. value
Ò
alarm
OU2
window function, normally open (Fno)
XX.X:
display value
A:
refilling
B:
min. monitoring
C:
max. monitoring
•
If the level is below rP1, output 1 switches until liquid is refilled. If SP1 is reached again, output 1 is
reset.
•
If the level is below FL2 or above FH2 or if there is a wire break, output 2 is reset (OFF) (→ alarm).
•
The logical operation between the outputs 1 and 2 indicates whether there is overflow or the actual
level is below the minimum level: