3. Mounting
To avoid malfunction a minimum
distance between the flow moni-
tor and bends, valves, changes in
cross-section or such like must be
observed:
• Min. 5 x pipe diameter
upstream (A),
• min. 3 x pipe diameter down-
stream (B).
(This information refers to laminar
flow.)
Step 1
Weld the adapter into the pipe.
The installation depth depends
on the pipe wall thickness. The
bush should be inserted so that
the figure corresponding to the
wall thickness is flush with the
outside pipe wall and can be seen
fromall sides.
In the case of horizontal pipes
the bush should be welded at an
angle of 45°.
11
ENGLISH
4
4
6
10
8
10
4
8
6
45
°
45
°
D
A
B
min.
5 x D
min.
3 x D