After mounting, wiring and setting check whether the unit operates
correctly.
Faults displayed during operation:
Adjustable parameters
35
ENGLISH
Installation and set-up / operation
Technical informations / Parameters
(Flashing): short circuit in the switching output 1*
(Flashing): short circuit in the switching output 2*
Overload (above measuring range of P1 / P2)
Underload (below measuring range of P1 / P2)
(Flashing): short circuit in both switching outputs*
*The output concerned is switched off as long as the short circuit exists.
Short-circuit messages are displayed even if the display is switched off
(diS = OFF).
Switch-on point 1 / 2:
Upper limit value at which the output changes its switching
status.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automati-
cally reduced (rPx is set to the minimum setting value).
CAUTION:
The entered values for SPx/rPx are initial values. The
effect of the set switch points on the output stage is influenced
by the analogue input P2 and the respective parameter settings
(
IxP2, LS1, LS2
).
The display always shows the unchanged initial values.
Setting ranges:
→
page 58.