• The pressure sensor detects the
system pressure (P1)
,
• shows the current system pressure on its
display
• and generates
2 output signals
according to the set output con-
figuration.
• In addition an
analogue signal (P2)
which can be configured can
be supplied. It has influence on the switch points preset in the basic
settings or on the preset window and on the pressure values dis-
played (display P2 or P1-P2).
24
Function and features
p-switching (
PnP
)
Output polarity (applies to both
switching outputs)
Switching function
(function can be selected for
each output separately)
n-switching (
nPn
)
hysteresis function / N.O. (
Hno
)
hysteresis function / N.C. (
Hnc
)
window function / N.O. (
Fno
)
window function / N.C. (
Fnc
)
+
-
P1
LSx
SPx
rPx
+ +
+
InP2
ILP2
IHP2
IEP2
-
OUT
U/I ext
(P2)
LSx = off
Dmod=P1
Dmod
=P2
Dmod=P1-P2
P1: system pressure
P2: analogue input signal
InP2: type of signal (I or U)
ILP2: initial value of the input signal
IHP2: final value of the input signal
IEP2: pressure value to which the
final value of the analogue
signal set in IHP2 is to
correspond
OUT: output signals
SPx: switch-on points
rPx: switch-off points
LSx: linear change in the switching
thresholds
Dmod: display mode
( P1 or P2 or P1 minus P2 is
displayed)