28
Configuration of output 1
4 switching functions can be set:
-
Hno
= hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
Analogue start point
Measured value at which 4 mA / 0 V is provided.
ASP is active only if
OU2
=
I
or
U
.
Analogue end point
Measured value at which 20 mA / 10 V is provided.
Minimum distance between ASP and AEP = 25%
(scaling factor 4).
AEP is active only if
OU2
=
I
or
U.
Configuration of output 2
4 switching functions and 2 analogue signals can be set:
-
Hno
= hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
-
I
= analogue output 4 ... 20 mA
-
U
= analogue output 0 ... 10 V
1)
Measured value = displayed value * 10
2)
display
-.XX
=
-0.XX
∆
P
=
increments
∆
P
max
min
max
min
ASP
AEP
0.1
100
24.0
75.0
-1.0
bar
10
1450
350
1090
-10
PSI
1)
0.01
10.0
2.40
7.50
-0.10
MPa
2)
Setting
range