For installation in pipes:
•
The inside pipe diameter (d) must be at least 100 mm�
-
Only install the unit in metal pipes�
-
For installation in connection pieces:
•
The diameter of the connection piece (d) must be at least 50 mm�
-
The height of the connection piece (h) must not exceed 40 mm�
-
d
d
h
The maximum level must not ex-
•
ceed the limit of the block distance
(BD = 30 mm)� If it is exceeded by
more than 10 mm, malfunctions
can occur�
Remedies: arrange for a spout; in-
stall the unit in a connection piece�
BD
Do not install the unit in the immediate vicinity of a fill opening� If possible,
•
install a fill pipe (A) in the tank� Minimum distance between the fill pipe and the
rod = 50 mm; higher for rod lengths > 70 cm and in case of heavy soiling (→
6�1�1)�