background image

9

UK

In case of operation as 3-wire unit only A2 must be used as output 

(OSSD). Otherwise the safety function of the sensor will be impaired or 

prevented.

 

► Connect output A1 to supply voltage�

 

► Make absolutely sure to exclude cross faults and short circuits between the 

supply voltage and output A2 by means of appropriate installation!

The indicated values regarding the safety function (→ 10 Technical data) remain 

unchanged�

8  Operation

8.1  Switching status of the outputs
8.1.1  The safe state

The safe state is when at least one of the outputs A1 and A2 (OSSD) is switched 

off (zero-current state: logic "0")�  

If one of the outputs A1 and A2 is switched off, the subsequent safety-related logic 

unit must bring the complete system into the state defined as safe� 

8.1.2  The switched state

If the damping element is in the enable zone and if there is no sensor error, both 

outputs A1 and A2 (OSSD) are enabled (logic "1")�

8.1.3  Output data

The output data are based on the input data to EN 61131-2 type 1 or 2:

logic "1"

≥ 15 V

2���15 mA

≥ 11 V

15���30 mA

logic "0"

≤ 5 V

leakage current 0�2 mA

8.1.4  Cross faults

•  A cross fault between both outputs (A1 and A2) is detected by the fail-safe 

sensor and leads to switching off the outputs (OSSD) at the next safety 

request� The outputs A1 and A2 remain switched off until the error has been 

removed�

•  A cross fault between one of the two outputs (A1 or A2) and the supply voltage 

leads to switching off the other output (A2 or A1) in case of a safety request�

Содержание Efector 100 GG712S

Страница 1: ...Original operating instructions Fail safe inductive sensor GG712S 704229 01 06 2010 UK...

Страница 2: ...ation 7 7 Electrical connection 8 7 1 Operation as 4 wire unit 8 7 2 Operation as 3 wire unit 8 8 Operation 9 8 1 Switching status of the outputs 9 8 1 1 The safe state 9 8 1 2 The switched state 9 8...

Страница 3: ...d safety regulations The instructions contain information about the correct handling of the product Read the instructions before use to familiarise yourself with operating conditions installation and...

Страница 4: ...the unit please contact the manufacturer Tampering with the unit is not allowed Disconnect the unit externally before handling it Also disconnect any independently supplied relay load circuits After...

Страница 5: ...d please contact one of the ifm branch offices 4 Functions and features The fail safe inductive sensor GG712S detects metal without contact Safety function SF The safe state output stage switched off...

Страница 6: ...x 18 x 1 mm made of FE360 mild steel and flush installation to IEC 60947 5 2 the enable zone is in the range of 1 5 mm The safe switch off distance sar is 7 mm The enable zone is different if damping...

Страница 7: ...nt there may be no close zone 6 Installation The unit can be flush mounted according to IEC 60947 5 2 type I1A18SP2 Ensure the unit cannot work loose Maximum tightening torque 30 Nm Adhere to the inst...

Страница 8: ...fault the supply voltage must not exceed a maximum of 40 V DC This requires the safe separation between power supply and transformer For unit with cULus approval and the scope of validity cULus The d...

Страница 9: ...s switched off the subsequent safety related logic unit must bring the complete system into the state defined as safe 8 1 2 The switched state If the damping element is in the enable zone and if there...

Страница 10: ...ay LED status Operating status Outputs A1 OSSD A2 OSSD Signal Power no voltage supply both outputs switched off 0 0 Signal Power undervoltage 1 0 0 0 Signal Power overvoltage both outputs switched off...

Страница 11: ...nts of SIL 2 to IEC 61508 SILcl 2 to IEC 62061 PL d to EN ISO 13849 1 flush mountable Operating voltage 24 V DC 19 2 30 V Short circuit protection yes Reverse polarity protection yes Current rating 10...

Страница 12: ...level max 2000 m Ionising radiation not permissible Rate of temperature change 0 5 K min Ambient temperature 25 70 C for service life 87600 h 10 40 C for service life 175200 h Relative air humidity 5...

Страница 13: ...on unit or PLC Core colours BK black BN brown BU blue WH white Remarks Unless stated otherwise all data refer to the 18 x 18 x 1 mm reference target plate to IEC 60947 5 2 FE360 mild steel over the wh...

Страница 14: ...utput A1 or A2 and the supply voltage Error in the sensor detected Remove the cross fault Replace the unit No close zone Due to its characteristics material form size the damping element displaces the...

Страница 15: ...switching elements proximity switches IEC 61508 2000 IEC 62061 2005 UL 508 14 Terms and abbreviations CCF Common Cause Failure DC Diagnostic Coverage MTTFD Mean Time To Dangerous Failure OSSD Output...

Отзывы: