background image

5

UK

 

► Adhere to the principle of normally closed operation for all external safety 

circuits connected to the system�

 

► In case of faults within the fail-safe sensor which result in the defined safe 

state: take measures to maintain the safe state when the complete control 

system continues to be operated�

 

► Replace damaged units�

3  Items supplied

1 fail-safe sensor GG712S with 2 mounting nuts M18, 

1 operating instructions GG712S, ident no� 704229�
If one of the above-mentioned components is missing or damaged, please contact 

one of the ifm branch offices�

4  Functions and features

The fail-safe inductive sensor GG712S detects metal without contact� 
Safety function SF: The safe state (output stage switched off; logic "0") is achieved 

when undamping greater than or equal to the safe switch-off distance s

ar

 (→ 10 

Technical data)�  

Also observe the notes on installation of the sensor (→ 6 Installation)�
The fail-safe sensor conforms to Performance Level d to EN ISO 13849-1 as well 

as the requirements SIL 2 to IEC 61508 and fulfils SILcl 2 to IEC 62061�  
The unit corresponds to the classification I1A18SP2 to IEC 60947-5-2 for flush 

installation (→ 6 Installation)�
The fail-safe inductive sensor has been certified by TÜVNord� 

Содержание Efector 100 GG712S

Страница 1: ...Original operating instructions Fail safe inductive sensor GG712S 704229 01 06 2010 UK...

Страница 2: ...ation 7 7 Electrical connection 8 7 1 Operation as 4 wire unit 8 7 2 Operation as 3 wire unit 8 8 Operation 9 8 1 Switching status of the outputs 9 8 1 1 The safe state 9 8 1 2 The switched state 9 8...

Страница 3: ...d safety regulations The instructions contain information about the correct handling of the product Read the instructions before use to familiarise yourself with operating conditions installation and...

Страница 4: ...the unit please contact the manufacturer Tampering with the unit is not allowed Disconnect the unit externally before handling it Also disconnect any independently supplied relay load circuits After...

Страница 5: ...d please contact one of the ifm branch offices 4 Functions and features The fail safe inductive sensor GG712S detects metal without contact Safety function SF The safe state output stage switched off...

Страница 6: ...x 18 x 1 mm made of FE360 mild steel and flush installation to IEC 60947 5 2 the enable zone is in the range of 1 5 mm The safe switch off distance sar is 7 mm The enable zone is different if damping...

Страница 7: ...nt there may be no close zone 6 Installation The unit can be flush mounted according to IEC 60947 5 2 type I1A18SP2 Ensure the unit cannot work loose Maximum tightening torque 30 Nm Adhere to the inst...

Страница 8: ...fault the supply voltage must not exceed a maximum of 40 V DC This requires the safe separation between power supply and transformer For unit with cULus approval and the scope of validity cULus The d...

Страница 9: ...s switched off the subsequent safety related logic unit must bring the complete system into the state defined as safe 8 1 2 The switched state If the damping element is in the enable zone and if there...

Страница 10: ...ay LED status Operating status Outputs A1 OSSD A2 OSSD Signal Power no voltage supply both outputs switched off 0 0 Signal Power undervoltage 1 0 0 0 Signal Power overvoltage both outputs switched off...

Страница 11: ...nts of SIL 2 to IEC 61508 SILcl 2 to IEC 62061 PL d to EN ISO 13849 1 flush mountable Operating voltage 24 V DC 19 2 30 V Short circuit protection yes Reverse polarity protection yes Current rating 10...

Страница 12: ...level max 2000 m Ionising radiation not permissible Rate of temperature change 0 5 K min Ambient temperature 25 70 C for service life 87600 h 10 40 C for service life 175200 h Relative air humidity 5...

Страница 13: ...on unit or PLC Core colours BK black BN brown BU blue WH white Remarks Unless stated otherwise all data refer to the 18 x 18 x 1 mm reference target plate to IEC 60947 5 2 FE360 mild steel over the wh...

Страница 14: ...utput A1 or A2 and the supply voltage Error in the sensor detected Remove the cross fault Replace the unit No close zone Due to its characteristics material form size the damping element displaces the...

Страница 15: ...switching elements proximity switches IEC 61508 2000 IEC 62061 2005 UL 508 14 Terms and abbreviations CCF Common Cause Failure DC Diagnostic Coverage MTTFD Mean Time To Dangerous Failure OSSD Output...

Отзывы: