22
8.6 LED indicators DTE604
The following LED indicators only apply to DTE604�
8.6.1 LED SF
LED red
LED green
Status
Note
off
off
no voltage supply
check the voltage supply
off
on
normal operation
-
flashing
off
error at channel level
- overload
- temperature
- internal fault
on
off
error at device level
- undervoltage
- temperature
flashing
flashing
self-test
starting phase of the device
8.6.2 LED BF
LED red
LED green
Status
Note
off
off
no voltage supply
check the voltage supply
off
flashing
connection to host
controller exists, there is
no data exchange
-
off
on
connection to host
controller exists,
data exchange running
-
flashing
off
connection to host
controller exists, there is no
valid configuration
check configuration
on
off
no connection to the
host controller
check connection
flashing
flashing
self-test
starting phase of the device