11
UK
2
1
4
3
2
1
3
1
2
4
5
Pin 4-pole M12 make connector
①
1 L+ / supply voltage
2 not used
3 L- / supply voltage
4 C/Q IO-Link
Pin 5-pole M12 female connector
②
1 L+
2 0...10 V analogue output 2
3 L-
4 0...10 V analogue output 1
5 not used
1: IO-Link side
2: Actuator side
The device must not be externally supplied via the 5-pole M12 output
socket ②.
Always use the provided connection cables to connect other devices to the
converter.
Also see application examples
Tighten the M12 connectors firmly to ensure the protection rating.
.
►
Connect the device as required (arrow shows the position of the coding).
►
Tighten coupling nut.
Tightening torque: min. 0.6 Nm (tightening by hand), max. 1.5 Nm (using
a torque wrench)
►
For removal, loosen the coupling nut and simultaneously press the
connector against the device.
►
If used in harsh environments, further tighten the coupling nut by
another notch using a torque wrench (across the flats 14).