background image

CompactModul Metall CR2033

16

8  Parameter and EMCY object overview

Automatic saving of the communication and unit parameters can be activated or 

deactivated by means of the "save all parameters" entry (see object directory, 

index 1010)� When the value 0x02 is entered into SIdx 01, all parameters are auto-

matically saved if changes were made� 

With the value 0x00 there is no automatic saving, i�e� changed parameters will only 

be valid until the unit is switched off or until the next reset is made�
With the function "restore" (see object directory, index 1011) the parameters (ex-

cept the baud rate and the node ID) can be assigned to the factory default values� 

With the next power on they become valid�

8.1  Parameter list

Parameter

Index 

in object 

directory

Default

(factory preset)

Change

automatically 

saved

Change

effective

Manufacturer Specific Profile Area; index 2000 to 5FFF

I/O Configuration

2000

binary inputs/outputs

adjustable

after PreOp

PWM Frequency

2001

0x64 (100 Hz)

adjustable

after PreOp

Node-ID *)

20F0, 20F1

0x20 (0d32)

yes

after a reset

Baud rate *)

20F2, 20F3

0x04 (125 kBit/s)

yes

after a reset

Communication Profile Area; Index 1000 to 1FFF

COB-ID Synch Objekt

1005

0x80

adjustable

after a reset

Communication Cycle

1006

0x00 (Off)

adjustable

immediately

Guard Time

100C

0x00 (Off)

adjustable

immediately

Life Time Factor

100D

0x00

adjustable

immediately

Save Parameter

1010

0x02

(AutoSave ON)

yes

immediately

COB-ID EMCY

1014

0x80 + Node-ID

adjustable

after a reset

Consumer Heartbeat 

time

1016

0x00 (Off)

adjustable

immediately

Producer Heartbeat time

1017

0x00 (Off)

adjustable

immediately

COB-ID Rec PDO 1

1400 01

0x200 + Node-ID

adjustable

after a reset

Trans Type Rec PDO 1

1400 02

0x01 (synchronous)

adjustable

immediately

COB-ID Rec PDO 2

1401 01

0x300 + Node-ID

adjustable

after a reset

Trans Type Rec PDO 2

1401 02

0x01 (synchronous)

adjustable

immediately

COB-ID Trans PDO 1

1800 01

0x180 + Node-ID

adjustable

after a reset

Trans Type Trans PDO 1

1800 02

0xFF (asynchronous)

adjustable

immediately

Event Timer Trans PDO1

1800 05

0x00

adjustable

immediately

COB-ID Trans PDO 2

1801 01

0x280 + Node-ID

adjustable

after a reset

Содержание CR2033

Страница 1: ...Device manual Input output module CompactModule metal CR2033 80269923 00 01 2018 UK...

Страница 2: ...5 6 Fuses 7 5 7 Examples for connection 8 6 Set up 9 6 1 PLC configuration in CODESYS 2 3 9 6 2 PLC configuration in CODESYS 3 5 10 6 2 1 Heartbeat configuration 10 6 2 2 SyncMonitoring 11 6 3 Electr...

Страница 3: ...art of the unit It contains texts and drawings concerning the correct handling of the module and must be read before installation or use Observe the information of the description Non observance of th...

Страница 4: ...ing to the tech nical specification indicated below Due to the additional self heating the housing walls can have high perceptible temperatures when touched in hot environments In case of malfunctions...

Страница 5: ...set function i e assignment of the parameters to the factory default values upon request The CR2033 I O module ist not approved for safety relevant tasks in the field of safety of persons factory defa...

Страница 6: ...ghtening torque of 1 2 Nm 5 3 M16 cable gland Use a suitable cable to ensure ingress resistance of the M16 cable gland If the M12 connectors are used for the device supply and CAN connection close the...

Страница 7: ...ording to the type of connection and jumper set tings The M12 plugs are designed for max 4 A the clamps for max 16 A 1 Supply via M12 CANin CANout plug 3 4 5 6 7 4 A 2 Supply via clamps not via M12 CA...

Страница 8: ...CompactModul Metall CR2033 8 5 7 Examples for connection Example 1 Example 2 Example 3 Example 4 jumper inserted...

Страница 9: ...terface is directly done from the application programmed with CODESYS 2 3 To do so the Electronic Data Sheet EDS is integrated via the CODESYS PLC configuration CODESYS dialogue PLC configuration exam...

Страница 10: ...e Device and click on In stall Select EDS file and click on Open In CODESYS 3 5 the devices are integrated as CiA remote devices in the de vice tree under a CANopen_Manager element The CANopen communi...

Страница 11: ...pplementing the SDO list in the CANopen configurator or during the operating time via the function block COP_SDOwrite The monitoring time is indicated in microseconds s 6 3 Electronic Data Sheet The E...

Страница 12: ...be linked using a jumper header GND and UB potentials linked upon delivery Cable entry via M16 cable gland Inputs Outputs 8 x M12 connector socket 5 pole CANin CANout 2 x M12 connector plug socket 5 p...

Страница 13: ...artbeat error if node guarding heartbeat is activated no synch objects if synch monitoring is activated IN yellow ON binary input switched OUT yellow ON binary output output switched ON analogue outpu...

Страница 14: ...s Switching voltage 10 32 V DC Switching current max 4 A Total current max 16 A PWM outputs PWM frequency 20 250 Hz Pulse duty factor 0 1000 Resolution 1 Switching current max 4 A referred to PWM valu...

Страница 15: ...01 CAN OUT 05 04 03 02 01 CAN Interface Supply 02 01 04 03 06 05 07 Inputs 05 04 03 02 01 05 04 03 02 01 05 04 03 02 01 05 04 03 02 01 05 04 03 02 01 05 04 03 02 01 05 04 03 02 01 Abbreviations CANH...

Страница 16: ...0x64 100 Hz adjustable after PreOp Node ID 20F0 20F1 0x20 0d32 yes after a reset Baud rate 20F2 20F3 0x04 125 kBit s yes after a reset Communication Profile Area Index 1000 to 1FFF COB ID Synch Objek...

Страница 17: ...hnical data Explanation of the abbreviations 0x hexadecimal number 0d decimal numerical value str String rw read write ro read only u8 unsigned 8 bit u16 unsigned 16 bit see also 12 Terms and abbrevia...

Страница 18: ...ode Only the first error of an error group is indicated If there is for example an error short circuit on channel 2 and then on channel 4 only the error which occured first is signalled CANopen does n...

Страница 19: ...gue output PWM 7 Configuration binary input channel 7 u8 rw 0x01 0 OFF 1 binary input 8 Configuration output channel 8 u8 rw 0x02 0 OFF 2 binary output 4 analogue output PWM 9 Configuration analogue i...

Страница 20: ...7 8 u8 rw 0x03 0 OFF 3 voltage 0 10 000 mV 6 ratiometric 0 1000 7 current 0 20 000 A 9 voltage 0 32 000 mV A binary input with analogue evaluation B binary input with analogue evaluation with diagnosi...

Страница 21: ...nufacturer specific 1003 0 Pre defined errorfield u8 ro 0x04 An error list with 4 entries is supported 1 Error history u64 ro 0x00 Error occured coded according to the EM CY list the last error is in...

Страница 22: ...e factory default values and are valid after the next reset 1014 0 COB ID Emergency u32 rw 0x00000080 Node ID EMCY is valid Bit 31 0 EMCY is not valid Bit 31 1 11 Bit ID Bit 29 0 ID 0x80 Node ID CAN i...

Страница 23: ...O 2 Analogue outputs 1 COB ID PDO 2 u32 rw 0x300 Node ID PDO is valid Bit 31 0 CAN ID of the 2nd Rec PDOs 2 Trans Type PDO 2 u8 rw 0x01 0x00 synch acyclic 0x01 0xF0 synch cylic Outputs are only update...

Страница 24: ...6411 Sldx 04 contains the preset value of the analogue output channel 8 The value is interpreted as pulse break ratio in depending on the configuration 1800 0 Trans PDO 1 u8 ro 0x05 Number of the entr...

Страница 25: ...1 Idx 6401 SIdx 01 contains the analogue value channel 1 2 2 Index im Objek tverzeichnis u32 ro 0x6401 02 Idx 6401 SIdx 02 contains the analogue value channel 3 4 3 Index im Objek tverzeichnis u32 ro...

Страница 26: ...pen communication profile describes the basic communication between network participants such as the transfer of process data in real time the exchange of data between units or the configuration stage...

Страница 27: ...nd data Access to the individual entries is possible via the index and S index Operational Operating state of a CANopen participant In this mode SDOs NMT commands and PDOs can be transferred PDO Proce...

Страница 28: ...ycle Sync object synchronisation object for simultaneous update in the complete network or for accepting process data of the respective parameterised PDOs Sync Windows time during which the synchronou...

Отзывы: