Remote I/O module 16 DI
AL4042
37
ü
IoT Core Visualizer has been launched.
ü
The [Processdata] menu is active.
u
Select the [io] > [port[n]] submenu (n: 1...8).
w
Menu page shows the digital input data of the port.
9.2.4.2 Reading counter values
Available information:
Name
Description
Value range
Access
[maincounter_value]
Current main counter value
0…4294967295
ro
1
[batchcounter_value]
Current batch counter value
0…65535
ro
1
1
read only
Requirements:
ü
IoT Core Visualizer has been launched.
ü
The [Processdata] menu is active.
u
Select the [io] > [counter[n]] submenu (n: 1...8).
w
The menu page shows current counter values of the counter module.
9.2.4.3 Controlling counter modules
Available control signals:
Name
Description
Values
Access
[reset]
Reset counter module (reset counter
and threshold values to default values)
• inactive: no action (default)
• active: reset
rw
1
[disable]
Disable counter module
• inactive: enable counter (default)
• active: disable counter
rw
1
[direction]
2
Set the counting direction for the main
counter and the batch counter
• up: up (default)
• down: down
rw
1
1
The parameter can only be changed if no connection to the fieldbus controller is active
2
only effective if operating mode of counter module =
CTDIR
Requirements:
ü
IoT Core Visualizer has been launched.
ü
The [Processdata] menu is active.
u
Select the [io] > [counter[n]] submenu (n: 1...8).
w
The menu page shows available services.
u
Set control signals.
u
Click on
to send the control signals to the device.
w
Control signals are executed.
9.2.4.4 Reading status and diagnostic information
Available information:
Name
Description
Value range
Access
[temperature]
Temperature of the device (value un de-
grees Celsius)
e.g. 52: 52°C
ro
1