IO-Link master with EtherCAT interface DataLine 4 ports IP 65 / IP 66 / IP 67
101
>
Port Configuration (0x8000)
34214
Manufacturer-specific settings of the IO-Link ports X01...X04
Selection of the IO-Link port via n (n = 0: port X01, n = 1: port X02,...)
Index
Sub-
index
Description
Possible values
Data type /
Access
0x80n0
Port Configuration
▪
0x04 Device ID
0x000000
...
0xFFFFFF
UINT32 / rw
▪
0x05 Vendor ID
0x0000
...
0xFFFF
UINT32 / rw
0x136:
ifm electronic
▪
0x20 IO-Link Revision
0x10:
IO-Link Revision 1.0
UINT8 / rw
0x11:
IO-Link Revision 1.1
▪
0x22 Cycle Time
UINT32 / rw
▪
0x24 Process Data In Length
UINT8 / rw
▪
0x25 Process Data Out Length
UINT8 / rw
▪
0x28 Master Control
0x00:
Deactivated
UINT16 / rw
0x01:
Digital Input
0x02:
Digital Output
0x03:
IO-Link
0x80n8
Vendor Specific Port Configuration
▪
0x01 Validation ID
0x00:
No check
UINT8 / rw
0x01:
V1.0 Device, no DS
0x02:
V1.1 Device, no DS
0x03:
V1.1 Device, Restore
0x04:
V1.1 Device, Restore
▪
0x02 Reconfigure
0x00:
No action
UINT8 / rw
0xFF:
Activate configuration
▪
0x03 Byte Swap
0x00:
No action
UINT8 / rw
0x01:
Byte swap
rw ... read and write