IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
58
>
13.2
EtherNet/IP
Content
Supported connection types ...................................................................................................................58
Parameter data .......................................................................................................................................59
Cyclic data ..............................................................................................................................................63
Acyclic data ............................................................................................................................................74
33674
>
13.2.1
Supported connection types
34410
Name
Configuration
Assemby
Input Assembly -
Instance
Output Assembly -
Instance
Exclusive Owner IO-Acyc-Diag
199
100
150
Exclusive Owner IO-Acyc
199
101
150
Exclusive Owner IO
199
102
151
Input only
199
100
193 (empty)
Listen only
199
100
192 (empty)