IO-Link Master with AS-Interface Interface StandardLine 2 Ports IP 65 / IP 66 / IP 67
17
>
7.2
LED indicators
34047
The device only has the following LED indicators:
>
7.2.1
Status LEDs
51964
The RDY LED indicates the status of the gateway.
The FLT LED shows the status of the AS-Interfaceconnection.
Status LED
Description
RDY
green
on
Status: OK
flashes 5 Hz
Status: Error
flashes (200 ms on,
800 ms off)
Status: Firmware update is running
off
Status: Gateway not running or gateway booting
FLT
red
on
AS-i connection error or AS-i default address is set
off
error-free
>
7.2.2
Voltage supply
58532
The port for the voltage supply has the AS-i LED. The LED indicates the status of the voltage supply:
Status LED
Description
AS-i
green
on
AS-i voltage supply is connected
off
no supply voltage or connected supply voltage is too low
>
7.2.3
IO-Link ports (Class A)
52923
Each IO-Link port Class A has 2 LEDs marked as IOL and DI. The LEDs indicate the status of the
IO-Link port.
Status LED
Description
IOL
yellow
off
Port configured as DI / DO: pin 4 (C/Q) = OFF
on
Port configured as DI / DO: pin 4 (C/Q) =ON
green
flashes 1 Hz
Port configured as IO-Link: no IO-Link device detected
flashes 2 Hz
Port configured as IO-Link: PROOPERATE state
on
Port configured as IO-Link: OPERATE state
red
flashes 1.2 Hz
Port configuration error or short circuit or overload
on
Transmission error
DI
yellow
off
Digital input : pin 2 (DI) = OFF
on
Digital input: pin 2 (DI) = ON