SmartPLC DataLine with Profinet device interface
134
>
Parameters: Flexible mode
41807
Parameter
Description
Values
Failsafe state
Behaviour of the slave outputs if
an interrupted fieldbus
connection is detected
Clear
outputs* =
All AS-i outputs are switched off in case
of an interrupted PROFINET
connection (value = 0).
Hold
outputs =
The outputs are held in the last valid
state that existed before the interrupted
connection was detected.
PROFINET alarms
Transmission of the PROFINET
alarms
Disable =
The PROFINETalarm data is NOT
written to the AS-i system.
Enable* =
The PROFINET alarm data is written to
the AS-i system.
Swap IO mapping slot 1...4
Slave assignment in the bytes
of the digital data
yes* =
Slave n+1 / slave n
no =
Slave n / slave n+1
AS-i param. download
Transmission of the slave
parameters when downloading
a configuration from the
PROFINET projection software.
Disable* = The following slave parameter data are
NOT downloaded to the device. The
parameters set in the device apply.
Enable =
Each time the PROFINET connection is
established, the following slave
parameter data are downloaded to the
device, activated in the AS-i slaves,
and stored non-volatilely.
Param. slave 1(A) AS-i master 1
…
Param. slave 31(A) AS-i master 1
Param. slave 1B AS-i master 1
…
Param. slave 31B AS-i master 1
Param. slave 1(A) AS-i master 2
…
Param. slave 31(A) AS-i master 2
Param. slave 1B AS-i master 2
…
Param. slave 31B AS-i master 2
Parameter data of the AS-i
slaves.
The set values are only
activated when the parameter
"AS-i param. download" is set to
the value "Enable".
P3..P0 =
P3..P0 =
…
P3..P0** =
…
P3..P0* =
2#0000 / 16#0
2#0001 / 16#1
...
2#0111 / 16#7
...
2#1111 / 16#F
* ... Default setting
** ... Default setting for A/B slaves
>
GSDML file
41479
To represent the Profinet gateway in a fieldbus projection software (e.g. Siemens Step7) a GSDML file
is provided.
The GSDML file for the
ifm
AS-i PROFINET gateway AC1403/04 is stored in the device and can be
loaded to the configuration PC via the web interface (
→
Download GSDML file
(
)). All parameter
and process data which is valid for the device is defined in the GSDML file.
On the Siemens Step7 object manager:
The object manager is part of the hardware configuration in Step7. It provides the device
catalogue containing all devices which are available for projection. The catalogue consists of
two parts. All non Siemens devices are listed in "Profinet
– Further fieldbus devices". These
devices are described using GSDML files which are imported into Step7.
>