AS-i Gateway with Profinet device interface
54
>
Change the digital output values manually
41602
WARNING!
The manual change of digital output values may cause undesired consequences to the
control process.
>
Risk of personal injury!
>
Risk of material damage to the machine/plant!
The operator is responsible for any consequences caused by the manual change of the
digital ouput values!
► Secure the concerned area.
► Only trained personnel is allowed to set outputs manually.
If the jog mode is deactivated: After changing the slave outputs the output values remain on
the changed values.
► Change the inverted outputs again immediately to the original values after the end of
the test!
To change the digital output values of an AS-i slave manually:
1 Enable manual access to the outputs
►
Set [Output access] parameter = Manual (→
Set the output access
2 Select the menu page
►
>
or
>
►
Select an AS-i slave (→
Slave selector
(→ S.
►
Select [Data] tab.
3 Set the digital output values manually
>
The group [Outputs] displays the current value of the digital output (binary and hexadecimal representation).
►
Set [Jog mode] as required. (→
Digital output
►
Change the desired output value bit by bit.
>
Selected value is applied.