AS-i Gateway with Profinet device interface
134
>
Parameters: Flexible mode
41807
Parameter
Description
Values
Failsafe state
Behaviour of the slave outputs if
an interrupted fieldbus
connection is detected
Clear
outputs* =
All AS-i outputs are switched off in case
of an interrupted PROFINET
connection (value = 0).
Hold
outputs =
The outputs are held in the last valid
state that existed before the interrupted
connection was detected.
PROFINET alarms
Transmission of the PROFINET
alarms
Disable =
The PROFINETalarm data is NOT
written to the AS-i system.
Enable* =
The PROFINET alarm data is written to
the AS-i system.
Swap IO mapping slot 1...4
Slave assignment in the bytes
of the digital data
yes* =
Slave n+1 / slave n
no =
Slave n / slave n+1
AS-i param. download
Transmission of the slave
parameters when downloading
a configuration from the
PROFINET projection software.
Disable* = The following slave parameter data are
NOT downloaded to the device. The
parameters set in the device apply.
Enable =
Each time the PROFINET connection is
established, the following slave
parameter data are downloaded to the
device, activated in the AS-i slaves,
and stored non-volatilely.
Param. slave 1(A) AS-i master 1
…
Param. slave 31(A) AS-i master 1
Param. slave 1B AS-i master 1
…
Param. slave 31B AS-i master 1
Param. slave 1(A) AS-i master 2
…
Param. slave 31(A) AS-i master 2
Param. slave 1B AS-i master 2
…
Param. slave 31B AS-i master 2
Parameter data of the AS-i
slaves.
The set values are only
activated when the parameter
"AS-i param. download" is set to
the value "Enable".
P3..P0 =
P3..P0 =
…
P3..P0** =
…
P3..P0* =
2#0000 / 16#0
2#0001 / 16#1
...
2#0111 / 16#7
...
2#1111 / 16#F
* ... Default setting