8.2 Explanation of the menu
SP1/rP1
Upper / lower limit value for system temperature at which OUT1 switches
SP2/rP2
Upper / lower limit value for system temperature at which OUT2 switches
OU1
Output function for OUT1:
Switching signal for the temperature limit values: Hysteresis function [H ] or
window function [F ], either normally open [ no] or normally closed [ nc]
OU2
Output function for OUT2:
Switching signal for the temperature limit values: Hysteresis function [H ] or
window function [F ], either normally open [ no] or normally closed [ nc]
Mmod
Measurement method (2-wire, 3-wire or 4-wire temperature sensors)
EF
Extended functions / opening of menu level 2
HI Maximum value memory for system temperature
LO Minimum value memory for system temperature
COF Zero-point calibration
dS1/dS2 Switch-on delay for OUT1 / OUT2
dr1/dr2 Switch-off delay for OUT1 / OUT2
FOU1 Behaviour of output 1 in case of an internal fault
FOU2 Behaviour of output 2 in case of an internal fault
P-n Output logic: pnp / npn
diS Update rate and orientation of the display
Uni Unit of measurement for system temperature
rES Restore factory settings