9.5.3 Setting of measured value damping
►
Select [dAP] and set the damping constant in seconds (t value 63 %)�
9.5.4 Setting of the error behaviour of the outputs
►
Select [FOU1] and set the value
-[On] = output 1 switches ON in case of a fault�
-[OFF] = output 1 switches OFF in case of a fault�
> For both values ([ON] and [OFF]) the counter stops counting in case of
a fault�
-[OU] = output 1 switches irrespective of the error as defined with the
parameters�
►
Select [FOU2] and set the value
-[On] = output 2 switches ON in case of a fault, the analogue signal
goes to the upper end stop value (22 mA)�
-[OFF] = output 2 switches OFF in case of a fault, the analogue signal
goes to the lower end stop value (3�5 mA)�
-[OU] = output 2 switches irrespective of the error as defined with
the parameters� The curve of the analogue signal corresponds to
IEC60947-5-7 (→ diagram in 4.6).
9.5.5 Setting of the standard pressure to which the measured and display
values for volumetric flow refer
►
Select [rEF�P] and set the requested standard pressure�
Setting range: 950���1050 hPa in steps of 1 hPa�
9.5.6 Setting of the standard temperature to which the measured and dis-
play values for volumetric flow refer
►
Select [rEF�T] and set the requested standard temperature�
Setting range: 0���25 °C in steps of 1 °C�
9.5.7 Setting of the low flow cut-off
►
Select [LFC] and set the limit value�
Setting range: 0�3���2�3 Nm³/h in steps of 0�1 Nm³/h�