9.3.2 Setting the switching limits
►
Select [SP1] / [SP2] and set the value at which the output switches�
►
Select [rP1] / [rP2] and set the value at which the output switches back�
rPx is always lower than SPx� The unit only accepts values which are lower
than SPx�
9.4 User settings (optional)
9.4.1 Zero-point calibration
►
Select [COF] and set a value between -5% and 5% of the final value of
the measuring range� The internal measured value “0” is shifted by this
amount�
As an alternative:
Automatic adaptation offset (setting range 0 bar ±5%); e�g� in the event of a
deviation of the mounting location of the sensor and the zero point level for
level measurement�
►
Make sure that no pressure is applied to the system�
►
Press [Mode/Enter] until [tCOF] is displayed�
►
Press [Set] and keep the buton pressed�
> The current offset value (in %) briefly flashes, then the current system
pressure (in the selected display unit) is displayed�
►
Release [Set]�
►
Press [Mode/Enter] briefly to confirm the new offset value�
9.4.2 Setting the delay time for the switching outputs
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2�
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2�
►
Select [dS1], [dS2], [dr1] or [dr2], set value between 0�1 und 50 s (at 0�0
the delay time is not active)�
9.4.3 Setting the output polarity
►
Select [P-n] and set [PnP] or [nPn]�