Information on the safe use in hazardous areas 

Function and features

• Use in hazardous areas according to the classification

(Group II, category 1 G / 2 G, apparatus for gas atmosphere).

The unit conforms to the requirements of EN50014, EN50020, EN50284
and EN60947-5-6.

• EC type test certificate

• Marking 

Installation / Setup

Only qualified staff with a knowledge of protection classes, regulations and
provisions for apparatus in hazardous locations may install, connect and set up
the units.
Check whether the classification (see "Marking" above and marking on the
unit) is suitable for the application.
• Connection only to intrinsically safe certified circuits or evaluation amplifiers

which do not exceed the following maximum values of the units:

• The wiring is indicated in the technical data sheet or on the type label.
• Permissible operating temperature of the application (referred to the maxi-

mum permissible power of 120 mW):

IRL

GB

ENGLISH

6

DMT 02 ATEX E028

U

i

= 15 V, 

I

i

= 50 mA, P

i

= 120 mW

II 1G / 2G

II 1G  EEx ia IIB T6  CE0158  Ta max = 70°C

Type NN****

II 1G  EEx ia IIB T5  CE0158  Ta max = 80°C

Type NN****

II 2G  EEx ia IIC T6  CE0158  Ta max = 70°C

Type NN****

II 2G  EEx ia IIC T5  CE0158  Ta max = 80°C

Type NN****

-20...+70°C

1G

IIB

T6

-20...+80°C

1G

IIB

T5

-20...+70°C

2G

IIC

T6

-20...+80°C

2G

IIC

T5