13
UK
"smoothed" by means of a mean filter; the result is a steady curve. Damping
can
be set by means of the parameter [dAP]
.
[dAP] indicates in seconds after what time 63 % of the final value is reached in the
event of a sudden jump. After 5 x [dAP] almost 100 % has been reached.
6.3.5 Probes for different tank heights
The unit can be installed in tanks of different sizes. Probes in different lengths are
available. To adapt to the tank height, each probe can be shortened. The minimum
probe length is 150 mm, the maximum probe length 2000 mm.
6.3.6 Defined state in case of a fault
• In case of a fault a state can be defined for each output.
• If a fault is detected or if the signal quality is below a minimum value, the
outputs pass into a defined state, according to NAMUR recommendation in
case of the analogue output. For this case the response of the outputs can be
set via the parameters [FOU1], [FOU2]
• Temporary loss of signal caused e.g. by turbulence or foam build-up can be
suppressed by a delay time (parameter [dFo]
time the last measured value is frozen. If the measured signal is received again
in sufficient strength within the delay time, the unit continues to work in normal
operation. If, however, it is not received again in sufficient strength within the
delay time, the outputs pass into the defined state.
In case of heavy foam build-up and turbulence, note the examples of how