In case of turbulances at the inflow side additional baffled pipes (B) are recom-
mended:
changes to the pipe diameter
B = 5 x pipe diameter
90° elbow
B = 5 x pipe diameter
two 90° elbows, one plane
B = 10 x pipe diameter
two 90° elbows, two planes
B = 15 x pipe diameter
valve, slide
B = 35 x pipe diameter
5.3 Mounting position
• Permitted mounting positions: pipe length vertical, any position (fig� 1, 2), pipe
length horizontal, unit vertical (fig� 3, 4), unit on side, pipe length left (fig� 5)�
• Avoid the mounting position shown in fig� 6 (unit on side, pipe length right)� If
the flow rate is low, the specified measurement accuracy cannot be adhered to�