Operating instructions 

Compressed air meter

SD8001

704842 /00

 

07 / 2010

UK

Содержание efector300 SD8001

Страница 1: ...Operating instructions Compressed air meter SD8001 704842 00 07 2010 UK...

Страница 2: ...llation 8 5 1 Installation location 8 5 2 Installation conditions 8 5 3 Mounting position 9 5 4 Installation in pipes 10 6 Electrical connection 10 7 Operating and display elements 11 8 Menu 12 8 1 Me...

Страница 3: ...values 17 9 4 4 Setting the error behaviour of OUT1 OUT2 17 9 5 Service Funktionen 18 9 5 1 Reading the min max values for volumetric flow 18 9 5 2 Reset all parameters to the factory setting 18 9 6 S...

Страница 4: ...at a standstill and no pressure is applied before mounting components into or removing them from compressed air equipment Improper or non intended use may lead to malfunctions of the unit or to unwan...

Страница 5: ...lising meter 9 3 1 or switching signal for preset counter 9 3 2 OUT2 2 selection options switching signal for volumetric flow limit value 9 2 2 or analogue signal for volumetric flow 9 2 3 4 2 Volumet...

Страница 6: ...hed after the time t the meter is automati cally reset and counting starts again output 1 does not switch Quantity monitoring not time dependent Settings ImPS quantity x ImPR no rTo OFF If the quantit...

Страница 7: ...tching state of the output stable if the volumetric flow varies slightly 4 6 Volumetric flow monitoring analogue function The analogue start point ASP determines at which measured value the output sig...

Страница 8: ...tion location Behind the cold dryer near the load If compressed air is fed into the main pipe through parallel pipes the unit should be mounted in the main pipe Installation after the maintenance unit...

Страница 9: ...o 90 elbows two planes B 15 x pipe diameter valve slide B 35 x pipe diameter 5 3 Mounting position Permitted mounting positions pipe length vertical any position fig 1 2 pipe length horizontal unit ve...

Страница 10: ...regulations for the installation of electrical equipment must be adhered to Voltage supply to EN50178 SELV PELV Disconnect power Connect the unit as follows 2 switching outputs 1 switching output 1 an...

Страница 11: ...3 and 5 flashing consumed quantity before the last reset in 103 standard cubic feet LED 4 current medium temperature in F LED 6 not used LED 7 LED 8 switching state of the corresponding output 9 Alph...

Страница 12: ...12 8 Menu 8 1 Menu structure Mode Enter Set scf current meter count in standard cubic feet scf stored meter count in standard cubic feet...

Страница 13: ...d Analogue signal 4 20 mA SP2 rP2 Maximum minimum value for volumetric flow at which OUT2 changes its switching status ASP Analogue start value for volumetric flow AEP Analogue end value for volumetri...

Страница 14: ...eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be reduced...

Страница 15: ...values Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Time out If during parameter setting no pushbutton is pressed for 15 s the unit exits the parameter setting mode The para...

Страница 16: ...quantity monitoring by pulse output Select OU1 and set ImP Select ImPS and set the volumetric flow quantity at which 1 pulse is provided 9 6 Select ImPR and set YES Pulse repetition is active Output...

Страница 17: ...he update rate and orientation of the display d1 update of the measured values every 50 ms d2 update of the measured values every 200 ms d3 update of the measured values every 600 ms rd1 rd2 rd3 displ...

Страница 18: ...e Enter briefly It makes sense to delete the memories as soon as the unit works under normal operating conditions for the first time 9 5 2 Reset all parameters to the factory setting Select rES then p...

Страница 19: ...4 000 000 scf Setting operation Ensure that OU1 is set to ImP Select ImPS press Set and keep it pressed The current numerical value flashes for 5 s then one of the 4 digits becomes active digit flashe...

Страница 20: ...h digit flashes unchanged for 3 s digit 1 becomes active again if the value of digit 1 is 0 8 1 2 3 no pushbutton pressed after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 If dig...

Страница 21: ...utput the output signal is at the maxi mum value during the power on delay time 10 1 Read the set parameters Press Mode Enter until the requested parameter is displayed Press Set briefly The unit disp...

Страница 22: ...rom time to time check the measuring probes visually for build up If necessary clean them at regular intervals To do so use a suitable cleaning liquid e g alcoholic solution Avoid mechanical damage to...

Страница 23: ...value 1 5 Measurement dynamics 1 300 Response time s 0 1 dAP 0 Temperature indication Measuring range F 32 140 Measuring error K 2 4 Operating temperature F 32 140 Medium temperature F 32 140 rel hum...

Страница 24: ...4 0 1 scfh 70 7945 30 7905 0 5960 1985 7945 5 ImPS min max 0 120 scf 4 000 000 scf Q step increment 13 Factory setting Factory setting User setting SP1 1500 rP1 1460 ImPS 0 120 ImPR YES OU1 Hno OU2 H...