9.3.3 Setting the analogue value for volumetric flow
► Select [Uni] and set the unit of measurement (→ 9.5.1).
► Select [SEL2] and set [FLOW]�
► Select [OU2] and set the function�
-[I] = current signal proportional to volumetric flow (4…20 mA)
► Select [ASP] and set the value at which the minimum value is provided�
► Select [AEP] and set the value at which the maximum value is provided�
9.4 Settings for consumed quantity monitoring
9.4.1 Settings for quantity monitoring via pulse output
► Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which 1 pulse is
provided (→ 9.7).
► Select [ImPR] and set [YES]�
> Pulse repetition is active� Output 1 provides a counting pulse each time
the value set in [ImPS] is reached�
9.4.2 Settings for quantity monitoring via the preset counter
► Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which output 1
switches (→ 9.7).
► Select [ImPR] and set [no]�
> Pulse repetition is not active� The output switches ON if the value set in
[ImPS] is reached� It remains set until the counter is reset�
9.4.3 Settings for program-controlled counter reset
► Select [rTo] and continue with a) or b)
a) Reset the counter manually
► Press [Set] until [rES�T] is displayed, then briefly press [Mode/Enter]�
b) Enter the value for time-controlled reset
► Press [Set] until the requested value is displayed (intervals from 1 hour
to 8 weeks), then briefly press [Mode/Enter]�
► Press [Set] until [rES�T] is displayed, then briefly press [Mode/Enter]�
9.4.4 Deactivation of the counter reset
► Select [rTo] and set [OFF]�The meter is only reset after overflow (= fac-
tory setting)�
Overflow: After the maximum value (9,999,999 Nm³) the counter is reset to 0�