Operating instructions 

Compressed air meter

SD6050

11406636

 / 00    1

1 / 2014 

UK

Содержание efector300 SD6050

Страница 1: ...Operating instructions Compressed air meter SD6050 11406636 00 11 2014 UK...

Страница 2: ...ng switching function 7 4 5 1 Hysteresis function 7 4 5 2 Window function 8 4 6 Volumetric flow or temperature monitoring analogue function 8 4 7 Setting of the standard conditions of the volume flow...

Страница 3: ...er settings optional 20 9 6 1 Setting of the standard unit of measurement for volumetric flow 20 9 6 2 Configuration of the standard display 21 9 6 3 Setting of measured value damping 21 9 6 4 Setting...

Страница 4: ...pplied Improper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connec tion set up operation and maintenance of...

Страница 5: ...red signals The unit displays the current process values It generates 2 output signals according to the parameter setting OUT1 4 selection options Switching signal for volumetric flow limit value 9 2...

Страница 6: ...ored So the possible data loss can be maximum 10 minutes Overflow After the maximum value 9 999 999 Nm the meter is reset to 0 The meter can be reset as follows Manual reset 9 3 3 Time controlled auto...

Страница 7: ...n be provided on output 2 Analogue functions 4 6 4 5 Volumetric flow or temperature monitoring switching function OUTx changes its switching status if it is above or below the set switching limits SPx...

Страница 8: ...of volumetric flow monitoring FE window 4 6 Volumetric flow or temperature monitoring analogue function 12 30 20 0 100 120 130 13 3 Characteristics of the analogue output to the standard IEC 60947 5 7...

Страница 9: ...the volume flow The unit is adjusted to a standard volume flow to DIN ISO 2533 i e volume flow at 1013 hPa 15 C and 0 relative air humidity The unit can be set to different standard conditions Via th...

Страница 10: ...be mounted before the oiler 5 2 Installation conditions To achieve the specified measurement accuracy the following installation condi tions must be adhered to defined inlet and outlet pipe lengths d...

Страница 11: ...l fig 3 4 unit on side pipe left fig 5 Avoid the installation position in fig 6 unit on side pipe right If the flow rate is low the specified measurement accuracy cannot be adhered to 1 2 3 5 4 6 5 4...

Страница 12: ...60947 5 6 Sample circuits 2 x positive switching 1 x positive switching 1 x analogue L L 3 BU 4 BK 2 WH 1 BN L L 3 BU 4 BK 2 WH 1 BN Pin 1 L Pin 3 L Pin 4 OUT1 Switching signal limit values for volume...

Страница 13: ...eset in 103 standard cubic metres values 9999 are displayed using the 103 exponential notation LED 5 green current medium temperature in C LED 7 yellow switching status of the corresponding output LED...

Страница 14: ...M S M M M S M S M S M S M Nl min S S Nm3 h S 15s S Nm s 15s S Nm3 15s S Nm3 15s C 15s M M M M M M M S M S M S M S M S S M S M S M M M M Mode Enter Set Nm3 current meter reading in Nm3 Nm3 stored meter...

Страница 15: ...tric flow or temperature DIn2 Configuration of the input Pin2 for counter reset EF Extended functions opening of menu level 2 HI LO Maximum minimum value memory for volumetric flow FOU1 Behaviour of o...

Страница 16: ...and diagnostic data and provides the possibility to set the parameters of the unit during operation In addition communication is possible via a point to point connection with a USB adapter cable You...

Страница 17: ...Setting of other parameters Start again with step 1 Finishing the parameter setting Press Mode Enter several times until the current measured value is displayed or wait for 15 s from menu level 1 or...

Страница 18: ...lect Uni and set the unit of measurement 9 5 1 Select OU1 and set the switching function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC Select SP1...

Страница 19: ...ings for quantity monitoring via the preset counter Select OU1 and set ImP Select ImPS and set the volumetric flow quantity at which output 1 switches 9 7 Select ImPR and set no Pulse repetition is no...

Страница 20: ...SP2 and set the value at which the output switches Select rP2 and set the value at which the output switches back 9 5 2 Setting the analogue value for temperature Select SEL2 and set TEMP Select OU2...

Страница 21: ...ing constant in seconds t value 63 9 6 4 Setting of the error behaviour of the outputs Select FOU1 and set the value On output 1 switches ON in case of a fault OFF output 1 switches OFF in case of a f...

Страница 22: ...es sense to delete the memories as soon as the unit operates under normal operating conditions for the first time 9 7 2 Reset of all parameters to factory setting Select rES Press Set and keep it pres...

Страница 23: ...first digit to right fourth digit Press Mode Enter briefly when all 4 digits are set As soon as the first digit flashes there are 3 options Briefly press Set 1 x The flashing digit increments 9 is fo...

Страница 24: ...the start value After this release Set briefly and start the setting again 10 Operation Correct operation and compliance with the measurement accuracy can only be ensured if the environmental conditi...

Страница 25: ...OL Measured value 120 of the final value of the measuring range UL Measured value 20 of the final value of the measuring range temperature Err Flashing error in the measuring probe or measured value 1...

Страница 26: ...001 ImPR YES OU1 Hno OU2 I SP2 FLOW 30 0 rP2 FLOW 29 6 SP2 TEMP 24 0 rP2 TEMP 23 8 ASP FLOW 0 0 AEP FLOW 75 0 ASP TEMP 0 0 AEP TEMP 60 0 DIn2 EDG FOU1 OFF FOU2 OFF dAP 0 6 rTo OFF diS d3 Uni nm3h SELd...