If no button is pressed for 15s during the setting procedure, the unit
returns to the run mode with unchanged values.
The unit can be electronically locked to prevent unwanted adjustment
of the set parameters: Press (in Run mode) both setting buttons for
10s. As soon as the indication goes out the unit is locked or unlocked.
Units are delivered from the factory in the unlocked state.
With the unit in the locked state
is indicated briefly when you try
to change parameter values.
After mounting, wiring and setting check whether the unit operates
correctly.
Adjustable parameters
→
page 24
Programming menu
→
page 3
Timeout
Locking / Unlocking
Display during
operation
Page 23
ENGLISH
1
Mode/Enter Set
Mode/Enter Set
Mode/Enter Set
Press the
Mode/Enter
button
several times until the
respective parameter
is
displayed.
Press the
Se
t button and keep it
pressed.
The current
parameter value
flashes
for 5s.
then the value is increased*
(incremental by pressing briefly or
scrolling by holding pressed).
Press the
Mode/Enter
button
briefly
(= acknowledgement).
The parameter is displayed again,
the set
parameter value
becomes effective
.
2
3
4
Change more parameters:
Start again with step 1.
Finish programming:
Wait for 15s or press the
Mode/Enter button until the current
measured value is indicated again.
*Decrease the value: Let the display of the parameter value move to the
maximum setting value. Then the cycle starts again at the minimum setting
value.
Programming
Installation and set-up / operation
switch on, initialisation
flashing: level close to the maximum measured value
level below the active zone
flashing = short circuit in the switching output
XXX / XX.X