8  Settings

Before the first set-up the empty adjustment must be carried out�

8.1  Set to the empty vessel

This adjusts the unit to both the empty vessel and the installation conditions (e�g� 

the set installation depth)� Previous settings are deleted�

 

► Empty the tank until the medium is at least 20 mm below the end of the probe�

 

► Press the programming button (OUT ON) for at least 2 s�

 

> The yellow LED flashes slowly (approx� 1 Hz) (= unit is in 

the adjustment mode)�

 

> After the adjustment process the yellow LED is lit con-

tinuously (= unit is in the operating mode, sensor zone 

not covered)�

8.2  Set to the full vessel

The empty adjustment is sufficient for media with a low dielectric constant (e�g� 

oils)� For aqueous media the sensitivity must be optimised by a full adjustment� 

The full adjustment does not change the settings of the empty adjustment�

 

► Fill the tank until the active zone of the unit is covered�

 

► Press the programming button (OUT OFF), keep it 

pressed for at least 6 s�

 

> The yellow LED flashes, after 6 s rapidly (approx� 2 Hz), 

(= device is in the adjustment mode)�

 

> After adjustment the green LED is lit continuously (unit is 

in the operating mode, sensor zone covered)�

Содержание efector160 LI214 Series

Страница 1: ...Operating instructions Binary level sensor LI214x 704776 00 10 2010 UK...

Страница 2: ...rinciple 4 4 2 Features of the unit 5 5 Installation 5 5 1 Installation location environment 5 5 2 Mounting 6 5 3 Set the installation depth 6 6 Electrical connection 7 7 Operating and display element...

Страница 3: ...t the product is suitable for your application without any restrictions If the operating instructions or the technical data are not adhered to personal injury and or damage to property can occur Insta...

Страница 4: ...te mounting accessories chapter 5 2 Installation procedure 4 Function 4 1 Measuring principle The unit operates to the capacitive measuring principle By direct contact with the medium the unit detects...

Страница 5: ...le detection of media with a very low dielectric constant e g oil The installation depth determines the level 5 3 The unit is virtually immune to almost any kind of build up on the probe The position...

Страница 6: ...ssure rating of 0 5 bar E43006 flange plate 65 80 with clamp adapter aluminium pressure rating of 0 5 bar E43007 flange plate 54 52x52 with clamp adapter aluminium pressure rating of 0 5 bar E43016 mo...

Страница 7: ...age supply to EN 50178 SELV PELV Disconnect power Connect the unit as follows 3 1 4 2 L L 1 4 3 Pin1 L Pin4 switching output NC Pin3 L Core colours of ifm sockets 1 BN brown 3 BU blue 4 BK black 7 Ope...

Страница 8: ...rocess the yellow LED is lit con tinuously unit is in the operating mode sensor zone not covered 8 2 Set to the full vessel The empty adjustment is sufficient for media with a low dielectric constant...

Страница 9: ...ation When the supply voltage has been applied the unit is in the operating mode It carries out its measurement and evaluation functions and switches the output Operation indication by LED LED Status...

Страница 10: ...nstant medium 1 8 Max tank pressure bar 0 51 Housing materials PP GF orange TPE U Materials wetted parts PP Protection IP 65 IP 67 Protection class II Ambient temperature C 0 60 Medium temperature oil...

Отзывы: