16
9.3.5 Setting the output polarity
►
Select [P-n], set [PnP] or [nPn]�
9.3.6 Setting the damping for the switching outputs
►
Select [dAP], set value between 0�01 ��� 4�00 s; (at 0�00 [dAP] time is
not active)�
dAP-value = response time between pressure change and change of the
switching status in seconds (s)�
Correlation between switching frequency and [dAP]: f
max
= 1 ÷ 2dAP��
9.3.7 Setting the damping for the analogue output
►
Select [dAA], set value between 0�01 ��� 4�00 s; (at 0�00 [dAA] time is
not active)�
dAA-value = response time between pressure change and change of the
switching status in seconds (s)�
[dAA] affects the IO-Link process data�
9.4 Service functions
9.4.1 Reading the min./max. values for the system pressure
►
Select [HI] or [LO], press [Set] briefly�
[HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press [Set] until [----] is displayed�
►
Press [Mode/Enter] briefly�