
10
Example: dSt for window function
1
Volumetric flow quantity Q reaches 0.5% of VMR → dSt starts, output becomes active.
2
dSt elapsed, Q reached good range → output remains active.
3
Q above SP (leaves good range) → output is reset.
4
Q again below SP → output becomes active again.
5
Q below rP (leaves good range) → output is reset again.
6
Q reaches again 0.5 % of VMR → dSt starts, output becomes active.
7
dSt elapsed, Q has not reached good range → output is reset.
8
Q reaches good range → output becomes active.
4.8 Customer-specific calibration (CGA)
This calibration changes the slope of the curve of measured values� It influences
the display and the outputs�
A
operating value for display and
output signals
Q
volumetric flow
MEW final value of the measuring
range
V0
curve of measured values
without calibration
V1,
V2
curve of measured values
after calibration
The change in the increase is indicated in percent� 100% corresponds to the fac-
tory calibration. It can be reset(→ 9.5.5).
Содержание efector 300 SU8001
Страница 1: ...Operating instructions Ultrasonic flow rate sensor SU8001 704851 00 07 2010 US...
Страница 16: ...16 8 Menu 8 1 Menu structure Mode Enter Set gal current meter count in gal gal stored meter count in gal...
Страница 28: ...28 11 Scale drawing 1 Display 2 Connector electrical connection 3 Marking direction of flow...