IFM Electronic efector 300 SU8001 Скачать руководство пользователя страница 1

Operating instructions 

Ultrasonic flow rate sensor

SU8001

704851 / 00 

 

  07 / 2010

US

Содержание efector 300 SU8001

Страница 1: ...Operating instructions Ultrasonic flow rate sensor SU8001 704851 00 07 2010 US...

Страница 2: ...Start up delay dSt 9 4 8 Customer specific calibration CGA 10 5 Installation 11 5 1 Installation location 11 5 2 Installation in pipes 13 5 3 Protection against high medium temperatures 14 6 Electrica...

Страница 3: ...the output logic 22 9 5 4 Customer specific calibration of the curve of measured values 22 9 5 5 Calibration reset 23 9 5 6 Setting the start up delay 23 9 5 7 Setting the damping of the measured val...

Страница 4: ...un wanted effects in your application That is why installation electrical connection set up operation and mainte nance of the unit must be carried out by qualified personnel authorised by the plant o...

Страница 5: ...totalising meter 9 3 1 or switching signal for preset counter 9 3 2 OUT2 4 selection options switching signal for volumetric flow limit value 9 2 2 or switching signal for temperature limit value 9 4...

Страница 6: ...tity monitoring with pulse output Output 1 provides a counting pulse if the value set in ImPS is reached 9 3 1 4 3 2 Consumed quantity monitoring with preset meter 2 types of monitoring are possible T...

Страница 7: ...t by means of the distance between SPx and rPx SPx maximum value rPx minimum value 1 2 HY hysteresis FE window examples for volumetric flow monitoring When set to the window function the set and reset...

Страница 8: ...etween 0 and 10 V It is also indicated Volumetric flow above the measuring range output signal 10 V Current output 4 20 mA example volumetric flow monitoring Factory setting Measuring range scaled MEW...

Страница 9: ...are 3 options The volumetric flow quantity increases quickly and reaches the switch point good range within dSt outputs remain active The volumetric flow quantity increases slowly and does not reach t...

Страница 10: ...ctive 7 dSt elapsed Q has not reached good range output is reset 8 Q reaches good range output becomes active 4 8 Customer specific calibration CGA This calibration changes the slope of the curve of m...

Страница 11: ...the unit so that the measuring pipe is always completely filled Arrange for inlet and outlet pipe lengths Disturbances caused by bends valves reductions etc are compensated for It applies in particula...

Страница 12: ...tion locations Directly in front of a falling pipe In a falling pipe FF flow direction At the highest point of the pipe system Directly in front of the spout of a pipe F flow direction On the suction...

Страница 13: ...r B into the pipe A 2 Place the seals C and install the unit according to the marked flow direction 3 Screw the adapter B with the threads D until it is hand tight 4 Tighten the two adapters in opposi...

Страница 14: ...equipment must be adhered to Voltage supply to EN50178 SELV PELV Disconnect power Connect the unit as follows Pin1 Ub Pin3 Ub Pin4 OUT1 Switching signal limit values for volumetric flow Switching sig...

Страница 15: ...LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits indication of the current volumetric flow if SELd FLOW is set indication of the meter count if SELd TOTL is set...

Страница 16: ...16 8 Menu 8 1 Menu structure Mode Enter Set gal current meter count in gal gal stored meter count in gal...

Страница 17: ...ure AEP Analogue end value for volumetric flow or temperature DIn2 Configuration of the input pin 2 for meter reset EF Extended functions opening of menu level 2 HI LO Maximum minimum value memory for...

Страница 18: ...am eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be redu...

Страница 19: ...ess Mode Enter Set for 10 s Loc is displayed During operation Loc is briefly displayed if you try to change parameter values Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Tim...

Страница 20: ...nction normally closed Select SP2 and set the value at which the output switches Select rP2 and set the value at which the output switches back 9 2 3 Scaling of the analogue value for volumetric flow...

Страница 21: ...vals from 1 hour to 8 weeks Press Mode Enter briefly 9 3 4 Switch off the meter reset Select rTO and set OFF The meter is only reset after overflow factory setting 9 3 5 Settings for meter reset by an...

Страница 22: ...ement providing the highest accuracy 9 5 2 Configuration of the standard display Select SELd and determine the standard process category FLOW display shows the current volumetric flow value in the sta...

Страница 23: ...d determine the value On output 2 switches ON in case of an error the analogue signal goes to the upper end stop value OFF output 2 switches OFF in case of an error the analogue signal goes to the low...

Страница 24: ...0 999 9 gal 3 3 1 0 0 0 9 9 9 9 1 gal 1 000 9 999 gal 4 3 5 1 0 0 0 9 9 9 9 10 gal 10 000 99 990 gal 5 3 5 1 0 0 0 9 9 9 9 100 gal 100 000 999 900 gal 6 3 5 1 0 0 0 9 0 0 0 1000 gal 1 000 000 9 000 0...

Страница 25: ...t kept pressed 1 0 1 2 Wait 3 s do not press any button The digit following on the right flashes becomes active 8 1 2 3 no pushbutton pressed after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 If t...

Страница 26: ...nc If output 2 is configured as analogue output the output signal is at the final value of the measuring range during the power on delay time 10 1 Read the set parameters Press Mode Enter briefly to s...

Страница 27: ...Set briefly The latest measured values are displayed IOE Flow sensor faulty Loc Setting pushbuttons locked parameter change rejected VMR final value of the measuring range 10 4 General operating cond...

Страница 28: ...28 11 Scale drawing 1 Display 2 Connector electrical connection 3 Marking direction of flow...

Страница 29: ...n load for voltage output k 2 Pulse value 0 02 9000 10 Pulse length s min 0 3 max 2 Power on delay time s 10 Flow monitoring gpm gph Measuring range 0 00 26 44 0 1585 Resolution 0 02 1 Display range 0...

Страница 30: ...tance M 100 500 V DC Shock resistance g 20 DIN IEC 68 2 27 11ms Vibration resistance g 5 DIN IEC 68 2 6 55 2000 Hz EMC IEC 1000 4 2 ESD 4 8 KV IEC 1000 4 3 HF radiated 10 V m IEC 1000 4 4 Burst 2 KV I...

Страница 31: ...mPR YES OU1 Hno OU2 I SP2 FLOW 20 02 rP2 FLOW 16 02 SP2 TEMP 136 5 rP2 TEMP 112 0 ASP FLOW 0 00 AEP FLOW 24 02 ASP TEMP 14 0 AEP TEMP 161 0 DIn2 EDG CGA 100 FOU1 OFF FOU2 OFF dSt 0 0 P n PnP dAP 0 6 r...