can alter the parameter value by pressing the "Set" pushbutton and
confirm the new value by pressing the "Mode/Enter" pushbutton. The
internal sensing, processing and output functions of the unit continue
as if in Run mode with the original parameter values unless a new
value is confirmed. The unit returns to the Run mode when no push-
button has been pressed for 15 s.
Adjustable parameters
35
ENGLISH
Technical information / Operation / Parameters
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SPx is only active if
OUx
=
Hno
,
Hnc
,
Fno
or
Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching
status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automa-
tically reduced (rPx is set to the minimum setting value).
rPx is only active if
OUx
=
Hno
,
Hnc
,
Fno
or
Fnc.
Setting ranges:
(standard volume flow):
in steps of
Nm
3
/min
Nm
3
/h
0.01
0.11 ... 11.67
0.05 ... 11.61
6 ... 700
3 ... 696
SP1 / SP2
rP1 / rP2
1
Pulse / Counter settings
Determines the pulse value / value for the preset counter.
Setting range
: 0.01 0 ... 4 000 000 Nm
3
Pulse length: min. 0.043 s / max. 2 s.
ImPS
is only active if OU1 =
ImP.
Setting of the value (
→
page 31)