UK
Field modules DP
33
Process data
The analogue output module generates output signals in a range of 0���20 mA� The
output current is output by the module with a resolution of up to 16 bits�
Pprocess data
Measured value
hex
decimal
0x0000
0
0 mA
0x3FFF
16383
10 mA
0x7FFF
32767
20 mA
Adjustment of the measuring values at 4���20 mA
Process data
Measured value
hex
decimal
0000
0
4 mA
3FFF
16383
12 mA
7FFF
32767
20 mA
Feature register (R32)
The basic settings of the module can be modified in the feature register� In order to
write to the register, it is required to remove the write protection in the code word
register�
Bit
Value
Description
2
0
Watchdog timer active
A
(default)
1
Watchdog timer inactive
3 and 4
Reserved
5
0
Mode: 0���20 mA
A
(default)
1
Mode: 4���20 mA
6 and 7
Reserved
9 to 15
Reserved