Field modules DP
14
5.1.4 Analogue input modules
The data mapping of all analogue input modules is identical�
Evaluation in the MOTOROLA format (default mapping)
Address
Input data
Output data
Word
High byte
Low byte
-
-
0
Channel 1 / DB 0
Channel 1 / DB 1
-
-
1
Channel 2 / DB 0
Channel 2 / DB 1
-
-
2
Channel 3 / DB 0
Channel 3 / DB 1
-
-
3
Channel 4 / DB 0
Channel 4 / DB 1
-
-
Evaluation in the Intel format (DB = data byte)
Address
Input data
Output data
Word
High byte
Low byte
-
-
0
Channel 1 / DB 1
Channel 1 / DB 0
-
-
1
Channel 2 / DB 1
Channel 2 / DB 0
-
-
2
Channel 3 / DB 1
Channel 3 / DB 0
-
-
3
Channel 4 / DB 1
Channel 4 / DB 0
-
-
5.1.5 Analogue output modules
The data mapping of all analogue output modules is identical�
Evaluation in the MOTOROLA format (default mapping)
Address
Input data
Output data
Word
-
-
High byte
Low byte
0
-
-
Channel 1 / DB 1
Channel 1 / DB 0
1
-
-
Channel 2 / DB 1
Channel 2 / DB 0
2
-
-
Channel 3 / DB 1
Channel 3 / DB 0
3
-
-
Channel 4 / DB 1
Channel 4 / DB 0