IO-Link master
44
26.3 Inserting I/O devices in the hardware configurator
►
Select the Profinet device in the hardware catalogue and move it to the Profbus
network using drag & drop�
26.4 IO-Link devices
The IO-Link devices have a module in slot 1 in which nine slots are configured�
Subslot 1 contains the status/control module which has 4 bytes of input data and
4 bytes of output data� These are shown in the IOLM_Status table (input) and
IOLM_Control table (output)�
IOLM_Status
Byte
Byte 0
Byte 1
Bit
7
6 5 4 3 2 1 0 7 6 5 4 3 2 1
0
Port
8
7 6 5 4 3 2 1 8 7 6 5 4 3 2
1
Meaning
COM states
PD valid states
Byte
Byte 2
Byte 3
Bit
7
6 5 4 3 2 1 0 7 6 5 4 3 2 1
0
Port
8
7 6 5 4 3 2 1 8 7 6 5 4 3 2
1
Meaning
Digital input states of C/Q
UA states
(pin 2)
Digital input states
of DI (pin 2)
IOLM_Control
Byte
Byte 0
Byte 1
Bit
7
6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Port
8
7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
Meaning
COM Cntrl
Reserved
Byte
Byte 2
Byte 3
Bit
7
6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Port
8
7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
Meaning
Digital output control of C/Q
Reserved
The corresponding submodules (analogue converters, digital inputs/outputs, IO-
Link sensors) can be configured in subslots 2 to 9 using drag and drop�
The other slots are configured as [Digital Input] by default� They must be removed if anything else
needs to be configured�