For programming terminals 6 and 7 must be linked, e.g. by means of
a key switch.
If no key is pressed during the programming/setting process for
approx. 15s, the unit will change into the operating mode with
unchanged parameter values.
12
P14
display brightness
0 ... 9 = level of brightness
5
P16
basic setting
1 = all parameter values are set to the basic setting
0
P18
input block for preset
0 = preset can be changed
1 = preset cannot be changed (blocked)
0 0
(V1 = 0
V2 = 0)
P19
limitation of the counting frequency in the VRD mode
0 = max. counting frequency =10 Hz
(max. count value: ± 32768)
1 = max. counting frequency = 20 kHz
1 1
(IN-A = 1
IN-B = 1)
P21
relay switches if value of the preset value is positive or
negative
0 = active; 1 = not active
1
P99
display of the current software version and the version
number
P15
external reset/preset
0 = preset if pulse on terminal 13
1 = reset if pulse on terminal 13
1
P12
fleeting time relay H1
0.1s ... 9.9s adjustable in steps of 0.1s
1,0
P13
fleeting time relay H2
0.1s ... 9.9s adjustable in steps of 0.1s
1,0
P11
output performance of the relay
X
0
= H1 switches at 0
0
X = H2 switches at 0
X
1
= H1 switches at preset
1
X = H2 switches at preset
X
2
= H1 switches at
≥
preset, de-energises at < preset
2
X = H2 switches at
≥
prese, de-energises at < preset
X
3
= H1 switches at
≤
preset, de-energises at > preset
3
X = H2 switches at
≤
preset, de-energises at > preset
0 4
= H1 switches at 0 and sets autopreset (preset 1)
4 0
= H2 switches at preset 1 - preset 2
0 5
= H1 switches at preset 1 and sets autoreset (0)
1 1