7.1  System parameters
7.1.1  FOx

Function Output (switching function of the outputs 1/2)

1

Relay energised (transistor output switched) when the current value is below the 

switch point SPx (signalled state: "minimum speed"/"blocked")�

2

Relay de-energised (transistor output blocked) when the current value is below the 

switch point SPx (error message: "underspeed "/"blocked")�

3

Relay energised (transistor output switched) when the current value is above the 

switch point SPx (signalled state: "rotational speed reached")�

4

Relay de-energised (transistor output blocked) when the current value is above the 

switch point SPx (error message: "overspeed")�

5

Relay is energised (transistor output switched) within a frequency range (acceptable 

range)�

6

Relay is de-energised (transistor output blocked) within the frequency range� 

With the functions 5 and 6 a frequency range above and below the switch point SPx 

is defined in connection with the parameter 

HYx

 (hysteresis)�

SPx = (f

max

 + f

min

) ÷ 2 

HY = ((SP - SP

min

) ÷ SP) x 100 [%]

Values

1���6

Default settings

FO1 = 2
FO2 = 3

7.1.2  SOx

Store Output (latching function outputs 1/2)

When this parameter is active, the respective output does not switch back automatically 

but must be reset�
Values

0 = inactive
1 = front reset ([Enter/►] > 3 s)
2 = front reset and external reset

Default value

0 = inactive

Содержание DD2505

Страница 1: ...Operating instructions Monitor FR 2 FR 2N 7390954 00 01 2013 UK ...

Страница 2: ...8 4 1 Display stand by mode 9 5 Installation 9 5 1 Installation of the device 9 5 2 Installation of the sensors 10 6 Electrical connection 10 6 1 Terminal connection 10 6 2 Voltage supply power 10 6 2 1 AC supply 10 6 2 2 DC supply 11 6 3 Inputs 11 6 3 1 Connection of the sensors In1 2 11 6 3 2 Reset inputs reset 1 and 2 11 6 3 3 Typical input circuit F x 12 6 4 Outputs 13 6 4 1 Relay outputs Out1...

Страница 3: ...1 Programming example DT1 Delay Time output 1 19 8 2 Notes on programming 20 8 2 1 RUN mode 20 8 2 2 Time Out function 20 8 2 3 Numerical entries 20 8 2 4 Factory Reset 21 8 2 5 KEY function locking 21 9 Test mode 22 9 1 Activate the test mode 22 9 2 Terminate the test mode 22 9 3 Test parameters 23 10 Scale drawing 24 11 Technical data 24 11 1 Overview 24 11 2 Approvals standards 25 12 Maintenanc...

Страница 4: ...self with operating conditions installation and operation Keep this document during the entire duration of use of the device Adhere to the warning notes and safety instructions 1 1 Symbols used Instruction Reaction result Designation of pushbuttons buttons or indications Cross reference Important note Non compliance can result in malfunction or interference Information Supplementary note 1 2 Warni...

Страница 5: ...r the operating elements and at the terminals for the supply of connected sensors The wiring of all signals in connection with the SELV circuit of the device must also comply with the SELV criteria safety extra low voltage safe electrical isolation from other electric circuits If the externally supplied or internally generated SELV voltage is externally grounded the responsibility lies with the us...

Страница 6: ...of the additional internal heating the operating elements and the housing walls can have high perceptible temperatures when touched in hot environments 2 7 Tampering with the device In case of malfunction of the unit or queries please contact the manufacturer Any tampering with the device can seriously affect the safety of operators and machinery This is not permitted and leads to the exclusion of...

Страница 7: ...motors 4 Switching outputs 5 Signals depending on the selected switching functions WARNING The device is not approved for safety related tasks in the field of operator protection Using an electrical connection of the outputs from two or more units to achieve a redundant circuit they can also be used for safety related tasks All applicable technical standards must be followed ...

Страница 8: ...cted PRG Programming mode setting of the parameter values KEY Locking 1b Actual values and parameter values 5 digit numerical Rotational speed 0 60 000 RPM Pulses 0 1 1 000 0 Hz Outside the value ranges the display shows 1c Parameter abbreviation and units 3 digit alphanumeric 1d Display is in stand by mode no values visible 4 1 1e Display in display mode Symbol for wire break short circuit on the...

Страница 9: ... Panel for labelling F xN device with NAMUR input 4 1 Display stand by mode If no button is pressed for more than 10 minutes the device changes to the stand by mode Values and units are no longer visible The stand by mode can be identified by a flashing rectangle Even if no values and units are visible the device continues its monitoring function on the basis of the set parameters and switches the...

Страница 10: ...mA I 6 0mA Sensor supply 10 20 Terminal connection WARNING Do not use unconnected terminals such as terminal 9 as support point terminal 6 2 Voltage supply power Voltage supply see type label The device may only be operated using one of the possible voltage connections i e either terminals 7 8 AC or terminals 1 2 24 V DC All supply and signal cables must be laid separately Use a screened cable if ...

Страница 11: ...nsors The connection of mechanical switch contacts is not recommended since they tend to bounce and produce faulty pulses The terminals 5 6 can be used for the sensor supply or for the reset inputs only F x 6 3 2 Reset inputs reset 1 and 2 The start up delay can be started or a saved error can be reset via the reset inputs terminals 17 18 The internal 24 V DC voltage terminal 5 or an external 24 V...

Страница 12: ...s Note on F xN The 24 V DC signal voltage required for the reset inputs is not available to the F xN This must be taken from an external voltage source The reference point GND of the external power supply must be connected to terminal 1 of the monitor otherwise no switching operation is possible 6 3 3 Typical input circuit F x 70E U BB 24 V sensor supply npn pnp sensor supply 270E 270E 47n 1n0 1n0...

Страница 13: ... outputs Out1 2 The transistor outputs need an external voltage of 24 V DC on terminal 3 Connect the reference point GND of the external power supply to terminal 1 of the monitor Otherwise no switching operation is possible The SELV criteria safety extra low voltage must be met for the DC supply of the transistor outputs The DC supply cable L terminal 3 must be protected externally with a 315 mA T...

Страница 14: ...in the parameters arranged in columns RUN mode Parameter range and PRG mode DIM FO1 SP1 FO2 SP2 SO1 FW2 SO2 FW1 VER HY1 HY2 ST1 ST2 DT1 FT1 DT2 FT2 NC1 Input 1 RPM Hz Input 2 RPM Hz 1 2 A 3 B NC2 1 Display actual value input 1 2 Display actual value input 2 3 Back to the RUN mode A System parameters B Application parameters only F xN ...

Страница 15: ...output blocked when the current value is above the switch point SPx error message overspeed 5 Relay is energised transistor output switched within a frequency range acceptable range 6 Relay is de energised transistor output blocked within the frequency range With the functions 5 and 6 a frequency range above and below the switch point SPx is defined in connection with the parameter HYx hysteresis ...

Страница 16: ...FWx inactive 0 FWx active 1 FOx 5 relay de energised relay remains de energised FOx 6 relay energised relay de energised Values 0 inactive 1 active Default value 0 7 1 4 NCx Number of Cams on inputs 1 2 Number of cams detected per revolution On the basis of this value the monitor calculates the rotational speed measured frequency NCx displayed speed in RPM For frequency measurements NCx 1 should r...

Страница 17: ...ue determines the distance between the switch off point and the switch point SPx Prevents a possible chattering of the switching output In connection with the switching functions 5 and 6 FOx an acceptable range or an error range can be defined Values 0 0 1000 0 of the value for SPx Default value 5 0 7 2 3 STx Start Up Delay Time for outputs 1 2 Enables the suppression of error messages when a mach...

Страница 18: ...value is above or below the switch point for more than the time set here Values 0 0 1000 0 s Default value 0 0 no delay time 7 2 5 FTx Fleeting Time for outputs 1 2 If an event occurs the output changes its state during the set time and then switches back to the initial state Values 0 0 1000 0 s Default value 0 0 fleeting time not active ...

Страница 19: ...value 5 Acknowledgement of the set parameter value Enter 3 s 6 Return to the RUN mode Enter 3 s 8 1 Programming example DT1 Delay Time output 1 Operation Display Change from the RUN mode to the parameter range here 1 Briefly press Enter once The 1st parameter range is displayed CH1 RUN 0 0 DT1 CH1 RUN 15 0 DT1 CH1 RUN 1 CH1 RUN PRG 0 0 DT1 CH1 RUN PRG 15 0 DT1 Selection of the requested parameter ...

Страница 20: ...1 RUN mode During programming the unit internally remains in the RUN mode RUN indicator visible This means that until a new value is acknowledged with Enter the unit carries out its monitoring function on the basis of the previously set parameters and switches the relay and transistor outputs accordingly The monitoring function of the monitor is deactivated by continuously pressing Enter in the RU...

Страница 21: ... 5 KEY function locking The unit can be locked to prevent incorrect entries After locking only the actual value indication can be switched with the and buttons Parameter range and PRG mode can no longer be selected Locking Unlocking Press and simultaneously and hold them pressed The KEY indicator flashes Release the pushbuttons when the KEY indicator is continuously indicated Press and simultaneou...

Страница 22: ...e the test mode Apply the operating voltage and press Enter simultaneously The display indicates the parameter range 11 and TST In addition to the system and application parameters the parameters for the test frequencies are available Test parameters Display mode System application parameters SW1 TS1 TP1 TS1 TP1 Input 1 RPM Hz 1 TS2 TP2 Input 2 RPM Hz 2 SW2 TS2 TP2 3 1 Test frequency input 1 2 Tes...

Страница 23: ...cy Values 1 5 1 fast 5 slow Default value 1 TSx Test Start on input 1 2 Initial value of the test frequency Values 1 60 000 RPM or 0 1 1000 0 Hz Default value 50 RPM TPx Test Stop on input 1 2 Final value of the test frequency Values 1 60 000 RPM or 0 1 1000 0 Hz Default value 1500 RPM ...

Страница 24: ... types PNP NPN NAMUR NAMUR to EN 50227 Sensor supply 24 V DC 8 2 V DC Input frequency 5 kHz 5 kHz Relay outputs 2 changeover contacts potential free Switching current 6 A 6 A Switching voltage 250 V AC B300 R300 Transistor outputs PNP switched externally supplied Switching current 15 mA short circuit proof Switching voltage 24 V DC 20 Protection housing terminals IP 50 IP 20 Ambient temperature 40...

Страница 25: ... found at www ifm com Data sheet search Article number 11 2 Approvals standards EC declarations of conformity approvals etc can be downloaded at www ifm com Data sheet search Article number More information 12 Maintenance repair disposal The unit is maintenance free Do not open the housing as the device does not contain any components which can be repaired by the user The device must only be repai...

Отзывы: