Device Manual IO-Link Master with PROFINET interface CabinetLine 8 Ports IP 20 (AL1900)
05 / 2018
Operation
Replace IO-Link device
9.3
Replace IO-Link device
7775
To replace an IO-Link device:
Requirement:
>
IO-Link device is with factory settings.
>
IO-Link device supports IO-Link standard 1.1 or higher.
1 Set data storage
►
Set the following parameters of the IO-Link port:
Validation and Data Storage = [Type compatible V1.1 device with Restore]
►
Save changes.
2 Replace IO-Link device
►
Disconnect old IO-Link device from IO-Link master.
►
Connect new IO-Link device with the same IO-Link port of the AL1900.
>
IO-Link master copies parameter values from the data memory to the new IO-Link device.