35
ifm
Device Manual AS-i IO-Link-Gateway (AC5225) Firmware V1.16
2017-11-20
IO-Link services
Device group services
Event status code (with details)
Bit 7 = 1. There is detailed information about each event as an event identifier and an event code. Bits
0...5 indicate one event each.
Bit no.
Description
0
event 1
0 = event entries in the diagnosis data bytes 3...5 are not (no longer) valid.
1 = event entries in the diagnosis data bytes 3...5 are valid.
1
event 2
0 = event entries in the diagnosis data bytes 6...8 are not (no longer) valid.
1 = event entries in the diagnosis data bytes 6...8 are valid.
2
event 3
0 = event entries in the diagnosis data bytes 9...11 are not (no longer) valid.
1 = event entries in the diagnosis data bytes 9...11 are valid.
3
event 4
0 = event entries in the diagnosis data bytes 12...14 are not (no longer) valid.
1 = event entries in the diagnosis data bytes 12...14 valid.
4
event 5
0 = event entries in the diagnosis data bytes 15...17 are not (no longer) valid.
1 = event entries in the diagnosis data bytes 15...17 are valid.
5
event 6
0 = event entries in the diagnosis data bytes 18...20 are not (no longer) valid.
1 = event entries in the diagnosis data bytes 18...20 are valid.
6
reserved
7
event details
1 = consider the event identifier and the event code.