Device Manual AS-i IO-Link-Gateway (AC5225) Firmware V1.16
2017-11-20
AS-i parameters
Data assignment with P0=1
P3
reserved
0
reserved
1
reserved
The IO-Link device parameters are always directly changed in the IO-Link device which usually saves
this data non-volatilely.
Deviations between the projected IO-Link configuration (manufacturer, device and function IDs) and
the configuration of the connected devices (with the "plug & comm" mode deactivated) lead to a
peripheral-fault message of the AS-i field module.
If one of these IDs is projected with 0x0000, the configuration of this ID is
not
checked.
Upcoming alarm events in the device also lead to a peripheral fault message of the AS-i field module.
The type of treatment of unique events must be set beforehand in the service "gateway configuration".
>
4.2
Data assignment with P0=1
6210
With P0 = 1 (default) the device-specific default data assignment is used. In the following table we
show how the input and output ports are supplied:
>
4.2.1
Transfer switching signals
6211
Port no.
Description
1
switching signal on D0
2
switching signal on D1
The data are transferred cyclically (typical: 5 ms).
>
4.2.2
Transfer values
6212
Max. 4 input words and 4 output words are available per 16 bits for the transmission of parameter
values (depending on the device).
Port no.
Description of D0/D1
Description of the words
1
Bit 0 of the value on D0
words 1 + 2
2
Bit 0 of the value on D1
words 3 + 4
The data are transferred cyclically (typical: 160 ms per word).
>