IFEX Technologies GmbH
IFEX 3000 Impulse Fire Fighting Technology
Nr.:IF3000-100
Instruction Manual
Instructions for Use and Operation
IFEX 3035 and IFEX 3050
P a g e | 12
Hansestr.18 D-27419 Sittensen
Mobile Fire Extinguishing Equipment
Date: 20.11.12
P a g e
|
12
Note:
Should the mobile equipment be used for training,
it will suffice to fill the water
container without fire extinguishing agent and with water only. After training it is
important to refill the fire extinguishing agent container immediately and air pressure
bottles according to para 7.1, 7.2 and 7.3, to ensure the equipment is ready for action.
Filling Instructions
7. Filling of the fire extinguishing agent:
7.1 IFEX 3035 mobile fire extinguishing equipment = 35 L container:
a) Fill the container with fresh and clean water through the filling opening (30 Liter).
b) Pour 17,5 ml (+5%)
PL-2/94
- FC-201F in the container through the filling opening.
c) Fill the container with clean water 35l -5% Tolerance (-1,75l)!
d) Tighten the top filling closure firmly.
7.2 IFEX 3050 mobile fire extinguishing unit = 50 L container
a) Fill the container with fresh and clean water through the filling opening (45 Liter).
b) Pour 25 ml (+5%)
PL 2/94
- FC-201F in the container through the filling opening.
c) Fill the container with clean water 50l - 5% Tolerance (-2,50l)!
d) Tighten the top filling closure firmly.
7.3 Filling of the air pressure cylinder:
Check the air pressure level with a test manometer.
- Test as follows:
1.
Make sure the cylinder valve is closed.
2.
Remove the pressure regulator from the cylinder, adjust the test manometer,
open the valve slowly and read the pressure:
IFEX 3035 = 6 ltr./300 bar, Minimum pressure 180 bar/+20°C, if less, refill.
IFEX 3050 = 6 ltr./300 bar, Minimum pressure 270 bar/+20°C, if less, refill.