TECHNICAL MANUAL  

-

  

IE 326S-2L

  9

10. WARNINGS

IE 326S-2L detector is a reliable, high quality device, which needs periodic maintenance in order to operate properly

and not cause false alarms.

This smoke detector is particularly designed to initiate and activate emergency action, but will do so only when used

together with an authorized fire alarm system. This detector must be installed in compliance with the laws in force in the

country where the product is installed.

This smoke detector is meant to protect property, not life. Smoke detectors do not provide early warning of fire and can-

not detect gas, combustion particles, or flames.

Smoke detectors are components of professionally installed fire alarm systems.

SERVICING SCHEDULE:

Maintenance operation depends on ambient conditions and should be carried out in compliance with the laws in force

in the country where the product is installed.

Inspect detector periodically following below steps:

1.  Ensure the detector head is undamaged. Check plastic structure and insect filter.

2.  Ensure the smoke entry apertures are not obstructed by whatever objects.

3.  Clean the detector if there are deposits on it.

4. Ensure no equipment which may generate combustion products or fine airborne particles, has been installed nearby

the detector following last inspection. If so, then you should notify the Fire Safety Officer or other competent authority its

presence, as this may cause false alarms.

Detectors should be tested and maintained following the instructions in this manual. To be safe, they should be replaced

every ten years.

Do not disassemble sensor head or any other parts. This will void product warranty.

11. INSTALLATION

11.1 Base installation

If you use a jumper wire to connect the poles of terminal 2 and 5 when testing the detector line continuity,

make sure the jumper wire is removed before installing the detector head.

The end-of-line device should be compatible with the control unit.
Open area smoke detectors are intended for ceiling or wall mount in accordance with the fire directives in

your country.

Smoke detector base can be mounted directly onto an electrical box, such as an octagonal one (75mm,

90mm, or 100mm), a round one (75mm), or a square one (100mm), without using any type of mechanical adap-

ter.

11.2 Head installation

-  Align the components as shown below.

-  Match the detector head to the base and twist it clockwise to secure it.

-  Do not install the detector head until the area is thoroughly cleaned of construction debris, dusts, etc.

-  The maximum number of smoke detector installed over the same line is 32 units.

To prevent detector contamination and subsequent warranty cancellation, do not remove the smoke detector
plastic cover until the area is cleaned and dust free. DO NOT PAINT DETECTOR!

NOT SUITABLE FOR INSTALLATION IN AREAS WHERE AIR SPEED EXCEEDS 300ft/min.

One month after installation:

Routine Inspection (and every 3 months after)

Every 6 months:

Operational Test

Every 12 months:

Functional Test and Cleaning

Содержание ANTINCENDIO IE 326S-2L

Страница 1: ...MANUALE TECNICO TECHNICAL MANUAL Sensore di fumo convenzionale Conventional smoke detector mod IE 326S 2L 2531 CPR 232 1663 Norme Standards EN54 7 2000 A1 2002 EN54 7 2000 A2 2006 090010285 14...

Страница 2: ...ta a guasti in percentuali estremamente modeste come d altra parte avviene per ogni manufatto elettronico o meccanico Vista la destinazione di questo articolo pro tezione di beni e persone invitiamo l...

Страница 3: ...linea estetica piacevole e di basso profilo per non creare problemi di installazione anche in ambientazioni ricercate Il sensore IE 326S 2L dotato di un circuito elettronico particolarmente immune a...

Страница 4: ...n tentare di smontare le parti assemblate dal produttore Gli elementi con chiusura stagna non devono essere ma nomessi o aperti dall utente finale Eseguire le operazioni di manutenzione e ispezione co...

Страница 5: ...e essere difettoso o i cablaggi potrebbero non essere stati effettuati appropriatamente Ricontrollare i cablaggi o sostituire il sensore Per testare la funzionalit del sensore far penetrare sufficient...

Страница 6: ...NDICE 1 GENERALITA 3 2 CARATTERISTICHE TECNICHE 3 3 COLLEGAMENTI ELETTRICI 3 4 PRECAUZIONI E AVVERTENZE 4 5 INSTALLAZIONE 4 5 1 Installazione della base del sensore 4 5 2 Installazione del corpo del s...

Страница 7: ...es for every other electronic or mechanical Given the target of this article property and persons protection invite the user to proportion the protection level offered by the system to the actual risk...

Страница 8: ...design and low profile allow the detector to be installed in special demanding environments unobtru sively IE 326S 2L detector has also a built in electronic circuit featuring RF and electrical distu...

Страница 9: ...rity its presence as this may cause false alarms Detectors should be tested and maintained following the instructions in this manual To be safe they should be replaced every ten years Do not disassemb...

Страница 10: ...sh it indicates the non functioning of the detector or faulty wiring Re check the wiring or replace the detector if necessary Allow smoke from a cotton wick or a test smoke aerosol IESS AEROSOL to ent...

Страница 11: ...AL MANUAL IE 326S 2L 11 12 CONTENTS 7 GENERAL 8 8 TECHNICAL SPECIFICATIONS 8 9 WIRING DIAGRAM 8 10 WARNINGS 9 11 INSTALLATION 9 11 1 Base installation 9 11 2 Head installation 9 11 3 Operational test...

Страница 12: ...UAL Edizione Maggio 2012 rev Novembre 2014 May 2012 Edition rev November 2014 090010285 Le informazioni e le caratteristiche di prodotto non sono impegnative e potranno essere modificate senza preavvi...