Quick Installation Guide 

 
 

 
 
 
 

 
 
 
 

 
 
 
 

 
 
 
 

 
 
 
 

 
 
 
 

 
 
 
 

 
 
 
 

 
 

 

iTDC/iTDC-SR 

 

  Access Control Panel 

[Max 4 Door] 

 

Содержание iTDC

Страница 1: ...Quick Installation Guide iTDC iTDC SR Access Control Panel Max 4 Door ...

Страница 2: ...ts 1 IDENTIFYING SUPPLIED PARTS 2 2 RECOMMANDED CABLE TYPE AND PERMISSIBLE LENGTH 3 3 EARTH GND CONNECTION 4 4 DEVICE WIRING 7 5 REVERSE DIODE CONNECTION 15 6 SYSTEM INITIALIZATION 16 7 COMMUNICATION 16 8 PRODUCT MANUAL DOWNLOAD INFORMATION 22 ...

Страница 3: ... If any of these parts are missing contact your distributor Main Unit 1ea Quick Guide 1copy Diode 4ea Door Lock ALARM Guide 1Sheet Expansion I O Board EIO88 Keypad Option LCD Module Option TCP IP Module Option iTDC 26bit Wiegand Reader Compatible iTDC SR 34bit Wiegand Reader Compatible ...

Страница 4: ...Input iTDC iTDC SR Belden 9512 22 AWG 4 conductor shielded 300m Belden 9514 22 AWG 8 conductor shielded Door Lock Alarm Device Lock Alarm iTDC iTDC SR Belden 9409 18AWG 2 conductor unshielded 300m RS232 Cable Converter Host P C Belden 9829 24 AWG 2 twisted pair shielded 15m RS422 Cable iTDC iTDC SR iTDC iTDC SR iTDC iTDC SR Converter Belden 9830 24 AWG 3 twisted pair shielded 1 200m UTP Cable Host...

Страница 5: ... SR TO NEMA CASE Please refer to a figure below for Earth GND connection only applicable for NEMA package GND connection will avoid potential difference and also prevents any possible abnormal behavior caused by thunderbolt or surge Figure Earth GND connection when installing iTDC iTDC SR to NEMA case ...

Страница 6: ...ctpartof Nemacase Ground contact part is for connecting a plug Earth GND to the NEMA case Connect Earth wire of NFB using a metallic screw A circular lug must be used to tightly fix the screws 5 Ground contact part of power point Make sure to use power point with Earth GND connecting piece as shown in the figure above The size of IDTECK s NEMA case is 350mm X 399mm X 100mm Width X Depth X Height w...

Страница 7: ...potential difference and also prevents any possible abnormal behavior caused by thunderbolt or surge Please refer to the figure below for instruction of how to connect Earth GND Earth GND Figure Connection of Earth ground when installing a iTDC iTDC SR Earth GND Figure Earth GND connection for installation of multiple iTDC iTDC SR Please make sure that power is not being supplied to the controller...

Страница 8: ...dditional device such as door contact or exit button can be connected to input ports INPUT 1 INTPUT 7 of iTDC iTDC SR Wiring method may vary based on the number of doors to be controlled Please refer to below table for more details about how to wire an input device TIP I O board EIO88 is required for additional door control Maximum up to 4 doors Figure Input device wiring ...

Страница 9: ...1 GND of EIO88 Door Contact Connect one wire to Input 2 of EIO88 Connect the other wire to Input 2 GND of EIO88 Door 3 Exit Button Connect one wire to Input 3 of EIO88 Connect the other wire to Input 3 GND of EIO88 Door Contact Connect one wire to Input 4 of EIO88 Connect the other wire to Input 4 GND of EIO88 4 DOOR CONTROL Attach I O board EIO88 to iTDC iTDC SR before wiring Door 1 and 2 are con...

Страница 10: ...nductive material use insulation tape when wiring reader exit button and lock Make sure to cut cleanly to prevent exposure of cable core Use insulation tape to complete the wiring Interaction of exposed cable core with conductive materials frame must be avoided to prevent product damage Figure Connection of Earth GND for metal frame Figure Insulation taping to marked part Figure Connection of Eart...

Страница 11: ...larm Device Connection Connect COM port of Relay to DC 12V Connect NO port of Relay to wire of Alarm devices Connect GND port to wire of Alarm devices Figure Door Lock Alarm Device Connection You need to connect the diode 1N4001 1N4007 or Similar when connecting external devices to relay Power Fail Secure Mode This mode allows doors to be closed automatically when there is no power being supplied ...

Страница 12: ...ect wire of alarm to GND wire of power device Connect anti inverse voltage diode between wire and wire of alarm Wiring for door lock and alarm in Power Fail Secure Mode Door 1 Door Lock Connect 12V wire of DC12V power device to R1COM port of iTDC iTDC SR main board Connect wire of door lock to R1NO port of iTDC iTDC SR main board Connect wire of door lock to GND wire of DC12V power device Connect ...

Страница 13: ...OUT4 port of EIO88 4 Door Control Attach I O board EIO88 to iTDC iTDC SR before wiring Door 1 and 2 are controlled by main board of iTDC iTDC SR and door 3 4 are controlled by I O board EIO88 Door 1 Door Lock Connect to R1 port of iTDC iTDC SR main board Check the wiring type between POWER FAIL SAFE and POWER FAIL SECURE Alarm Connect to R2 port of iTDC iTDC SR main board Door 2 Door Lock Connect ...

Страница 14: ...ce to either Power Fail Safe or Power Fail Secure mode A separate power supply is required for 24V external relay Please refer to the figure below Figure Wiring for using 24V door lock or automatic door Make sure to use a separate power supply and an external relay Fail to do so may cause possible product damage Caution when using 24V door lock or automatic door ...

Страница 15: ...ernal Reader Reader 4 Connect 12V wire Red to 12V of READER 4 port of iTDC iTDC SR main board Connect GND wire Black to GND of READER 4 port of iTDC iTDC SR main board Connect D0 wire Green to D0 of READER 4 port of iTDC iTDC SR main board Connect D1 wire White to D1 of READER 4 of iTDC iTDC SR main board 3 Door Control If external reader and internal reader are connected to door 1 Attach I O boar...

Страница 16: ...ke sure to ground GND of external power and GND of iTDC iTDC SR as common Failed to do so may cause communication error Noise from outside can cause system troubles and may shorten the product lifetime RF reader can use external power 5 REVERSE DIODE CONNECTION If you connect an inductor Door Locks or Alarm device to the output relays there will be a high surge voltage created while the inductor i...

Страница 17: ...cleared and the basic setting values factory setting values will be reloaded Therefore the Initialization should be performed by authorized personnel only 7 COMMUNICATION 7 1 RS232 Communication Port Connection A 9 pin connector Serial communication connector female is required to connect the iTDC iTDC SR to a host computer via RS232 communication Please follow the instructions Connect RS232 TX po...

Страница 18: ...he converter and the device is too far Please follow the instructions below Connect RS422 TX of iTDC iTDC SR to RS422 RX port of converter Connect RS422 TX of iTDC iTDC SR to RS422 RX port of converter Connect RS422 RX of iTDC iTDC SR to RS422 TX port of converter Connect RS422 RX of iTDC iTDC SR to RS422 TX port of converter Plug in the RS232 9PIN connector of the converter to the COM1 or COM2 po...

Страница 19: ...TDC iTDC SR to RS422 RX of another iTDC iTDC SR Connect RS422 RX of one iTDC iTDC SR to RS422 RX of another iTDC iTDC SR Second you have to connect one of RS422 port of iTDC iTDC SR to RS422 RS232 converter Connect RS422 TX of the one iTDC iTDC SR to RX port of the converter Connect RS422 TX of the one iTDC iTDC SR to RX port of the converter Connect RS422 RX of the one iTDC iTDC SR to TX port of ...

Страница 20: ...mplete Figure TCP IP module Connection 2 As below figure connect LAN cable to TCP IP RJ 45 jack Figure LAN Connection 7 3 2 How to wire TCP IP Communication Optional TCP IP module is required for TCP IP communication between the iTDC iTDC SR and the PC Please follow the instructions below 1 Connect the LAN cable of the network system to the RJ45 jack of the iTDC iTDC SR 2 Set the board ID of the i...

Страница 21: ...cation select either RS232 or RS422 Figure TCP IP Converter between Host PC and iTDC iTDC SR INTERFACE iTDC iTDC SR ILAN422 RS232 TX CON2 RX RS232 DSUB9 RX CON2 TX RS232 DSUB9 GND CON2 GND RS422 TX CON3 RX RS422 CONNECTOR TX CON3 RX RS422 CONNECTOR RX CON3 TX RS422 CONNECTOR RX CON3 TX RS422 CONNECTOR ILAN422 ...

Страница 22: ... Connect iTDC iTDC SR No 1 controller s RS422 RX to iTDC iTDC SR controller s RS422 TX Connect iTDC iTDC SR No 1 controller s RS422 RX to iTDC iTDC SR controller s RS422 TX Connect TCP IP communication between iTDC iTDC SR and HOST PC Install and run iTDC iTDC SR Application Software Figure Bypass communication Second you have to connect all RS422 port of iTDC iTDC SR in parallel except iTDC iTDC ...

Страница 23: ...oad a manual for 4 At the bottom part of the product s page you selected click DOWNLOAD button and download the manual For un registered users of our homepage 1 Visit IDTECK s homepage www idteck com 2 Please click Member Join menu at the top of our homepage and register your details following the registration process 3 You can use your ID and P W after web administrator approves it Once it s appr...

Страница 24: ... Quick Installation Guide The specifications contained in this manual are subject to change without notice at any time 5F Ace Techno Tower B D 468 Gangseo Ro Gangseo Gu Seoul 07573 Korea Tel 82 2 2659 0055 Fax 82 2 2659 0086 E mail webmaster idteck com ...