IDT P9025AC Скачать руководство пользователя страница 7

REVISION  08/26/15

7

P9025AC FOD TUNING GUIDE

AN-886  

Option #2: “Good Enough” FOD

In many applications, it is not required to be WPC-compliant. This is especially true for applications where the transmitter and 
receiver will be designed as a pair, and no guarantee for interoperability with other devices is needed. By removing the 350 mW 
hard requirement for foreign object losses, it provides tremendous flexibility to use and adjust one of the pre-programmed FOD 
curves. This eliminates the need for costly testing and device configuration.

To aid in the selection of the most appropriate FOD curve and make offset adjustments, a working spreadsheet is available. The 
spreadsheet is titled P9025-R-EVK FOD Calculator and can be downloaded at 

www.idt.com/P9025AC-R-EVK

. The spreadsheet 

should be used in conjunction with following these steps:

1. Create a bench setup that allows for accurate current measurements and voltage measurements of the system under 

design.

2. P9025AC measurements should take place directly across the OUT capacitor and the current should be measured as 

it leaves the P9025AC OUT node (see 

Figure 4

).

3. P9038 current measurements should take place at any point along the input power line feeding the sense resistor and 

across the REG_IN pin capacitor (see 

Figure 4

).

4. Find the optimal alignment location by placing the Rx on the Tx and moving around the Tx surface until the input current 

to the Tx reaches the minimum RMS value while the Rx is connected to the Tx and the output is present and stable (This 
should typically occur at the point when the center Rx coil opening (inner diameter) is directly above the center of the 
opening in the Tx coil (inner diameter).

5. Move the Rx coil exactly 5mm away from the Optimal Alignment Location in any direction.

6. Measure and record the input current, input voltage, and output voltage while sweeping the output load from 0 mA to 

1000 mA in approximately 50mA steps. While doing so, fill in Columns B, C and D at each load current level listed in 
column A on the Measurements tab. The input and output power levels will be calculated for you. Ideally, this should be 
performed with the final assembled wireless Tx and Rx products being built and the opposite Tx or Rx IDT EVK. Enter 
these values in the left hand input table labeled First data set.

7. Move the Rx coil exactly 5mm away from the Optimal Alignment Location in any direction that is 90? Clock-wise or 

counter-clockwise from the direction chosen for step 5. For example, if the Rx was move +5mm in the x-direction in step 
5, move the Rx ±5mm in the y-direction in step 7. Repeat step 6, with the exception of entering the data in the right hand 
data entry table (Columns: N,O, and P) labeled Second data set.

a.  For fixed alignment systems, enter the same data collected in step 6 in the second table indicated in step 7 (enter 

the same data in both tables, First and Second data sets are identical).

8. Make sure that no cell in the Output Voltage (V) columns D and P turns RED in after entering all the data. If the Output 

Voltage columns turn RED the system is not performing properly and the new product should be debugged to determine 
the source of the excessive losses and they should be corrected before proceeding.

9. Check the fit of the resulting input power curve from of the system under test to the default curves displayed on the 

FOD_Curves tab of the spreadsheet or check the 'Delta from Pre-programmed Banks' table on the Measurements tab 
for a column that has very few or no red cells. (see 

Figure 5

)

a. If all the cells in at least one bank are within -350 mW of the difference of input power and reported power, the cells 

will be white with black text (no red). That is the best fit FOD curve bank and should be selected. The necessary 
FOD2 offset value will be displayed in green below the table and the appropriate FOD2 resistor should be installed 
to result in that offset (if no FOD2 cell is green, it means the required offset shift is beyond the trim range).

In this case, use the determined FOD1 bank that has the green highlighted number beneath the Bank # by setting 
the specified FOD1 resistance (found above the Bank#). Then, set the FOD2 resistor value as shown for that bank.  
None of the available pre-programmed Banks meet the FOD thresholds at all load levels.

b. If no banks are free from red cells (or cells that are white with orange text), that means one or more points spanning 

the load has a variation greater than the input power transmitted or less than -350 mW  from the input power 
compared to the pre-configured curves. The engineer has two options: look for a "good enough" fit where the 
variation exceeds 350 mW, or, come up with a custom set of values that will need to programmed into the device.

Содержание P9025AC

Страница 1: ...on the pre programmed FOD curve For WPC compliant systems the loss allowed due to foreign objects is 350 mW not including known losses due to the Tx and Rx systems For systems where WPC compliance is...

Страница 2: ...sfer and decode communication packets Respectively the Rx device measures the power that it is receiving i e delivering to the load and reports that value to the Tx module Since the Rx circuit and sys...

Страница 3: ...for exact values The Rx Reported Received Power vs Load Current graph is an indication of the power lost due to the electrical operations required for the Tx and Rx to function as the load current cha...

Страница 4: ...WER_FOD reported level This offset is applied by connecting an external resistor from pin FOD2 to GND and directly affects the received power level that is reported to the transmitter across the load...

Страница 5: ...At 0 9V the offset is 0 mW At 0 V the offset is 300mW and at 1 8V the offset is 300mW The Rx reported received power shift can be calculated using the following equation where VFOD2 is found using equ...

Страница 6: ...power value from the Rx Second the FOD1 pin on the P9025AC Rx should be connected to GND This will have the effect of selecting the pre programmed Bank 10 which maxes out the reported power level If...

Страница 7: ...left hand input table labeled First data set 7 Move the Rx coil exactly 5mm away from the Optimal Alignment Location in any direction that is 90 Clock wise or counter clockwise from the direction chos...

Страница 8: ...the recommended bank by highlighting the suggested FOD1 and FOD2 resistances to use under the Bank row The listed values in the FOD1 section are the largest reported power error contained within the...

Страница 9: ...REVISION 08 26 15 9 P9025AC FOD TUNING GUIDE AN 886 be filled in...

Страница 10: ...100 MDT BST Reference Testers should be used in conjunction with calibrated lab equipment These laboratories offer excellent Qi compliance FOD determination services and they are recommended Due to th...

Страница 11: ...license under intellectual property rights of IDT or any third parties IDT s products are not intended for use in applications involving extreme environmental conditions or in life support systems or...

Отзывы: