Pulse Count is the amount of times the detector needs to be triggered within a 20
second period before an alarm condition is sent.
When the 862-01-EX-35RC detector is in Normal Operation it will only send an alarm
after 120 seconds of inactivity in the detection area.
Pet Alley Mode allows a corridor beneath the detector that allows pets to move without
detection. Loosen the PCB screw and slide the PCB up or down to line up with either the Pet
Alley or Normal indicators according to the desired detection pattern.
PIR Lens
Tamper Switch
Walk Test Jumper
On – Enables Walk Test (LED is
enabled, Pulse Count set to 1)
Off – Normal Operation
Pulse Count Jumper
On – Sets Pulse Count to 2
Off – Sets Pulse Count to 4
PIR LED
Enabled in Walk Test Mode,
Disabled in Normal Mode
Supervision Jumper
J1 On – 90 mins
J1 Off – 12 hrs
IDS Wireless
Transmitter
Power Connector
Connect the battery
holder lead here.
Detector Inputs
Tamper & PIR inputs
come from the
detector.
Pet Alley Adjustment
Set the detector to Pet Alley
Mode or Normal.