5.3.3. Installation plan
To be provided by the customer:
- Reservoir pump with the relevant output
- Motor protection switch for reservoir pump
-
Water filter
- Water meter with shut-off valves
- Regulating valve
- Thermometer, if required
To avoid corrosion and frost damage of the plate heat exchanger located in the heat pump, IDM-
Energiesysteme instruct to install a safety heat exchanger for al ground water plants. Here the
heat pump groundwater circuit is decoupled via a safety heat exchanger by a brine circuit. This
means that any damage in the groundwater circuit or in the safety heat exchanger does not result
in any additional damage to the heat pump.
At ground water plants with high pumping heads have to use corrogated tube
hoses instead of flexible connection hoses, because of the occuring low-
pressure the flexible connection hoses could be tightened.
ca.1,3m
ca.
0,6m
min
0,5m
min
0,5m
T
T
m³/h
SAFETY heat -
exchanger set
flow meter
Brine intermediate
circuit
water flow meter
(if required for the
government),
else insert adapter
pipes out of stainless
/galvanized steel,
plastic
throttle valve
bypass pipe for
flushing the well
filter:
mesh width min 0,4mm
max 0,6mm
ground water flow direction
min. 15 m
dry well
suction-/
extraction well
Filling and flushing device
Inlet flow
Outlet flow