The two fault signals provide diagnostic feedback to the user’s control 
system. These use the common ground to provide HI or LOW signals. 
When both Fault Signals indicate HI, the EagleDrive is operating normally 
(no faults detected). Signals are driven with 5.6kohm pull-up resistors to the 
internal 5V and should be monitored with a high impedance device (R

load

 > 

100kohms).

Caution:

  Do not short Fault Signals to ground or EagleDrive will not 

operate properly.

Fault Signal Out

Fault 
Signal 1

Lead 8
Brown

Fault
Signal 2

Lead 7
Blue

Fault 
Description

Drive 
Condition

Reason for 
Fault

Remedy

0

0

Under 
Voltage

Disabled

Voltage 
supply less 
than 8.5V

Ensure proper supply voltage, 
check power and ground 
connections

0

0

Over 
Temperature

Operating

Internal 
component 
temperature 
greater than 
170º C

Reduce load or increase 
cooling

0

0

Logic Fault

Disabled

Drive cannot 
locate the 
magnets 
inside the 
pump

Ensure pump is correctly 
attached to EagleDrive

1

0

Internal Short

Disabled

Drive 
components 
have failed

Reset EagleDrive by 
disconnecting and restoring 
power supply connection, 
if problem persists, contact 
Micropump for a replacement.

0

1

Low Load 
Current

Operating

Drive 
components 
have failed

Reset EagleDrive by 
disconnecting and restoring 
power supply connection, 
if problem persists, contact 
Micropump for a replacement.

1

1

None

Operating

No Fault

CAUTION

1

2

3

4

5
7

8

9

6

MODEL DEMSE

1

2

3

4

5
7

8

9

6

MODEL DEELE

LEAD

FUNCTION

GRAY CABLE 

WIRES

BLACK CABLE 

WIRES

1

POWER

RED

RED

+12 to +36 VDC, Class 2 
(SELV), Reverse-polarity 

protected

2

SPEED PWM IN

VIOLET

YELLOW

Ground if not used

3

GROUND

BLACK

BLACK

Common isolated from motor 

housing

4

FAULT OUT

BROWN

BROWN

Fault Signal 1

5

FWD/REV

ORANGE

ORANGE

Forward (

fl

 oat and insulate), 

Reverse (ground)

6

FAULT OUT

BLUE

BLUE

Fault Signal 2

7

TACH OUT

GREEN

GREEN

5 V square wave-2 pulses per 

revolution

8

SPEED 0-5 IN

YELLOW

WHITE

Control signal in, 0-5 VDC

9

SHIELD

BARE

BARE

Connected to Common

EagleDrive Lead Wire Assignments

Содержание MICROPUMP EagleDrive DEELE

Страница 1: ...NSTALLATION OPERATION AND WARRANTY INFORMATION EAGLEDRIVE TM EagleDriveTM DEMSE EagleDriveTM DEELE Without Enclosure Without Enclosure DEMSN DEELN CALL TOLL FREE 877 742 2878 FOR SALES AND SUPPORT Return to BurtProcess com ...

Страница 2: ...and power cables The Power Supply Assembly means only the printed circuit board and the electronic or mechanical components located inside or on the power supply enclosure and the Pump head Assembly means all other parts of the product including but not limited to the rotor No warranty of any kind is made or shall be imposed with respect to any pump or parts 1 that have not been properly installed...

Страница 3: ...his Guide is to provide information to enable suitably qualified technicians and fitters to install operate and maintain the Micropump EagleDrive and common pump motor combinations Use the Guide when you have purchased a motor or pump motor combination This guide contains specific information for installation operation and maintenance of the EagleDrive and references some of the most common pump m...

Страница 4: ...low risk of external damage Hot Surfaces Under some operating conditions surface temperatures can exceed 90 C 195 F Do not touch products while operating Do not touch within 30 minutes of system shutdown to allow surfaces to reach safe handling temperature Description The EagleDrive is a brushless DC motor with integrated controller specially designed to be electromagnetically coupled to a variety...

Страница 5: ...rews 4 supplied with the EagleDrive Torque screws to 0 8 N m 7 in lbs Loose bolts may result in pump motor misalignment Tighten bolts appropriately Pump motor misalignment may result in weakening the sealing of the enclosure Drive housing seal described below is required for IP55 rating Assembly Unpacking and Storage The product should be located with the inlet below or even with the liquid level ...

Страница 6: ...tage source and the frequency counter if used will be forced to the same ground reference when connected to the EagleDrive Ensure only one earth ground is used to avoid ground loops Using The Tachometer Output The tachometer output can be monitored using a frequency counter The tachometer output is 0 5V square wave pulse that occurs twice per pump drive revolution To convert the tachometer output ...

Страница 7: ...te the magnets inside the pump Ensure pump is correctly attached to EagleDrive 1 0 Internal Short Disabled Drive components have failed Reset EagleDrive by disconnecting and restoring power supply connection if problem persists contact Micropump for a replacement 0 1 Low Load Current Operating Drive components have failed Reset EagleDrive by disconnecting and restoring power supply connection if p...

Страница 8: ... the EagleDrive by first setting the external control signal input to the minimum value then switch off the power supply Check that the unit runs down in a steady manner Close the inlet and discharge valves Drain the pump if it is to be shut down for long periods or installed in areas where the liquid may freeze Refer to the Maintenance section for instruction on draining Extended periods of dry r...

Страница 9: ...ump periodically The pump cannot be drained completely a certain amount of liquid will remain in the magnet cup area Ensure that the pump is either flushed with a suitable flushing agent or precautions are taken against the effect of any remaining liquid during servicing When the pump has been handling flammable toxic or hazardous fluid the pump internals must be properly decontaminated by suitabl...

Страница 10: ...r Out lead is connected to the positive input of the frequency counter Check that the common lead of the frequency counter is connected to the motor Common lead Check leads to ensure no short circuits are present Motor is stopped Ensure proper voltage has been applied to motor power leads Ensure proper control input is applied to Control Input lead Ensure control power supply common is connected t...

Страница 11: ... Current Nominal Voltage 25 C Ambient 2 9A 24 VDC Speed Control 0 to 5 VDC Tachometer Out 0 to 5 VDC square wave 2 pulse per revolution Thermal Shutdown 135 C Thermal Restart 120 C Storage Temperature 40 to 135 C Maximum Ambient Operating Temperature 85 C at max load Reversible Yes Weight 0 5 kg Power Output Nominal 52 W Model DEELE EagleDrive Pump Configurations EAGLEDRIVETM DEMSE GA Series GJR S...

Страница 12: ...98684 USA Tel 1 360 253 2008 Fax 1 360 253 8294 E mail info micropump idexcorp com Web www micropump com To purchase pumps parts or receive further information contact your local Micropump distributor or contact Micropump directly MICROPUMP AND THE MICROPUMP LOGO ARE TRADEMARKS OF MICROPUMP INC Your Micropump Distributor Is ...