GAP ANNUAL CLEANING AND TEST PROCEDURES FOR UNITS INSTALLED IN CANADA

 

Each year, your chemical dispenser must be cleaned and its backflow prevention performance verified.  As this 

device is an end

-

of

-

line device (versus an in

-

line device) and evidence of effective backflow prevention is 

determined visually, a two

-

minute pressure test is not necessary.

 

 

If the Flex

-

Gap device cannot readily be seen during the test procedure, the housing of the chemical dispensing unit 

must be removed during testing.  Apply the appropriate test procedure below as applicable for your chemical 

dispensing unit.

 

 

4 GPM VENTURIS

 

 

1.

 

Fill discharge hose with water by opening the valve.

 

2.

 

When water begins to exit the discharge hose turn off the water and raise the end of the hose above the 

Flex

-

Gap.

 

3.

 

Observe that water is exiting the Flex

-

Gap.

 

4.

 

If the water is exiting the Flex

-

Gap it has passed the test.

 

5.

 

If the water is not exiting from the Flex

-

Gap, replace the Flex

-

Gap sleeve as per the instruction manual and 

re

-

test.

 

6.

 

If the water is not exiting from the Flex

-

Gap after replacing the sleeve and re

-

testing, replace the complete 

Flex

-

Gap assembly and re

-

test.

 

7.

 

If the water is not exiting from the Flex

-

Gap after replacing the Flex

-

Gap assembly, disconnect the water 

supply and replace the complete unit.

 

 

1 GPM VENTURIS

 

 

1.

 

Remove the Fill Tube Spout and replace with a 4

-

foot length of 

1/2” 

ID hose. 

 

2.

 

Fill the discharge hose with water by opening the valve.

 

3.

 

When water begins to exit the discharge hose, turn off the water and raise the end of the hose above the 

Flex

-

Gap.

 

4.

 

Observe that water is exiting the Flex

-

Gap.

 

5.

 

If the water is exiting the Flex

-

Gap, it has passed the test.

 

6.

 

If the water is not exiting from the Flex

-

Gap, replace the Flex

-

Gap sleeve and re

-

test.

 

7.

 

If the water is not exiting from the Flex

-

Gap after replacing the sleeve and re

-

testing, replace the complete 

Flex

-

Gap assembly and re

-

test.

 

8.

 

If the water is not exiting from the Flex

-

Gap after replacing the Flex

-

Gap assembly, disconnect the water 

supply and replace the complete unit.

 

DISCLAIMER

 

Knight LLC  does not accept  responsibility  for  the mishandling,  misuse,  or  non

-

performance  of the described items 

when used for purposes other than those specified in the instructions. For hazardous materials information consult 

label, MSDS, or Knight LLC. Knight products are not for use in potentially explosive environments. Any use of our 

equipment  in  such  an  environment  is  at  the  risk  of  the  user,  Knight  does  not  accept  any  liability  in  such 

circumstances.

 

WARRANTY

 

All  Knight  controls  and  pump  systems  are  warranted  against  defects  in  material  and  workmanship  for  a  period  of 

ONE  year.  All  electronic  control  boards  have  a  TWO  year  warranty.  Warranty  applies  only  to  the  replacement  or 

repair of such parts when returned to factory with a Knight Return Authorization (KRA) number, freight prepaid, and 

found to be defective upon factory authorized inspection. Bearings and pump seals or rubber and synthetic rubber 

parts such as 

O

” 

rings, diaphragms, squeeze tubing, and gaskets are considered expendable and are not covered 

under  warranty.  Warranty  does  not  cover  liability  resulting  from  performance  of  this  equipment  nor  the  labor  to 

replace this equipment. Product abuse or misuse voids warranty.

 

FOOTNOTE

 

The information and specifications included in this publication were in effect at the time of approval for printing. Knight 

LLC  reserves  the  right,  however,  to  discontinue  or  change  specifications  or  design  at  any  time  without  notice  and 

without incurring any obligation whatsoever.

 

KNI GHT

 

LLC,

   

A Unit of IDEX Corporation  (www.knightequip.com)

 

Knight Headquarters

 

Tel: 949.595.4800

 

Fax: 949.595.4801

 

USA Toll Free

 

Tel: 800.854.3764

 

Fax: 800.752.9518

 

Knight Canada

 

Tel: 905.542.2333

 

Fax: 905.542.1536

 

Отзывы: